User Manual
IO-Link   
10.2 Design of a command point with ID key-operated switch 
  SIRIUS ACT 3SU1 pushbuttons and signaling devices 
222  System Manual, 02/2015, A5E03457306020A/RS-AB/002 
One of the authorization levels 1 ... 4 can be assigned to each individually encodable ID key. 
If the identification number of the key used is not found in the individual key list, it is assigned 
to the authorization level "Individual ID key".  
In this case, only output 4 is activated, and the illuminated surfaces on the ID key-operated 
switch flash yellow. 
The authorization level is assigned via the Port Configuration Tool 
S7-PCT
. 
Procedure: 
To add a new individually encodable ID key to the list of individually encodable ID keys, or to 
change the authorization level of an already added individually encodable ID key, the 
following steps are required: 
●  Use individually encodable ID key in the ID key-operated switches. 
●  Wait for detection of the ID key 
●  Write the system command "Set authorization level x"; "x" represents the authorization 
level assigned to the ID key used (value 0xAx in the data set (index) 2 - system 
commands or button in the Port Configuration Tool 
S7-PCT
) 
●  Check: Status of the individually encodable ID key (data set (index) 92 - diagnostics) 
●  Remove the ID key from the ID key-operated switch 
Settings 
Description 
161 
Define authorization level 1 for the individually encodable ID key. 
162   Define authorization level 2 for the individually encodable ID key. 
163 
Define authorization level 3 for the individually encodable ID key. 
164  Define authorization level 4 for the individually encodable ID key. 
Status of the individually encodable ID key (data set (index) 92 - diagnostics, byte 
19.0 ... 19.7) 
You will find additional information in Chapter "Data set (Index) 92 - diagnostics (Page 282)". 
Value 
Description 
0 
Individually encodable ID key detected. 
1 
Electronic module memory is full. 
2 
No valid individually encodable ID key used. 