User Manual
  AS-Interface 
  9.7 Configuring the AS-Interface 
SIRIUS ACT 3SU1 pushbuttons and signaling devices 
System Manual, 02/2015, A5E03457306020A/RS-AB/002 
195 
9.7.3
Addressing the AS-Interface modules for base mounting 
To address the AS-Interface modules for base mounting, connect the 
3RK1904-2AB02 AS-Interface addressing unit. 
3SU1400-2EK10-6AA0
 and 
3SU1400-2EJ10-6AA0
 AS-Interface modules 
Technical data 
3SU1400-2EK10-6AA0 
3SU1400-2EJ10-6AA0 
I
e
< 260 mA 
U
e
18.0 V ... 31.6 V 
AS-i slave profile IO / ID / ID2 
(HEX) 
7 / 0 / E  7 / A / E 
ID1 code (HEX) 
1 ... F 