Data Sheet

Surge voltage resistance rated value 4kV
Protection class IP IP66/IP67
Shock resistance 30g / 11 ms
● acc. to IEC 60068-2-27
30 g / 11 ms
Mechanical service life (switching cycles)
● typical
1000000
Electrical endurance (switching cycles) with contactor
3RH11, 3RT1016, 3RT1017, 3RT1024, 3RT1025,
3RT1026 typical
1000000
Electrical operating cycles in one hour with contactor
3RH11, 3RT1016, 3RT1017, 3RT1024, 3RT1025,
3RT1026
6000
Thermal current 10A
Material of the enclosure of the switch head metal
Reference code acc. to DIN EN 81346-2 B
Reference code acc. to DIN EN 61346-2 B
Continuous current of the C characteristic MCB 1A; for a short-circuit current smaller than 400 A
Continuous current of the quick DIAZED fuse link 10A; for a short-circuit current smaller than 400 A
Continuous current of the DIAZED fuse link gG 6A; for a short-circuit current smaller than 400 A
Locking force 2600N
● acc. to DIN EN ISO 14119
2000N
Repeat accuracy 0.05mm
Minimum actuating force in activation direction 30N
Length of the sensor 185mm
Width of the sensor 54mm
Number of CO contacts for auxiliary contacts 2
Operating current at AC-15
● at 24 V rated value
6A
● at 240 V rated value
3A
Operating current at DC-13
● at 24 V rated value
3A
● at 125 V rated value
0.55A
● at 250 V rated value
0.27A
Design of the interface for safety-related
communication
without
Enclosure
Design of the housing special design
Material of the enclosure metal
Coating of the enclosure cathodic immersion coating
Design of the housing acc. to standard No
Drive Head
Design of the operating mechanism 5 directions of approach
Design of the switching function positive opening
3SE5312-0SD11 Subject to change without notice
Page 2/
7