Data Sheet

Mechanical service life (switching cycles)
● typical
15000000
Electrical endurance (switching cycles)
● at AC-15 at 230 V typical
100000
Electrical endurance (switching cycles) with contactor
3RH11, 3RT1016, 3RT1017, 3RT1024, 3RT1025,
3RT1026 typical
10000000
Electrical operating cycles in one hour with contactor
3RH11, 3RT1016, 3RT1017, 3RT1024, 3RT1025,
3RT1026
6000
Thermal current 10A
Material of the enclosure of the switch head plastic
Reference code acc. to DIN EN 81346-2 B
Reference code acc. to DIN EN 61346-2 B
Continuous current of the C characteristic MCB 1A; for a short-circuit current smaller than 400 A
Continuous current of the quick DIAZED fuse link 10A; for a short-circuit current smaller than 400 A
Continuous current of the DIAZED fuse link gG 6A
Active principle mechanical
Repeat accuracy 0.05mm
Minimum actuating torque in activation direction 0.25N·m
Length of the sensor 281mm
Width of the sensor 56mm
Design of the switching contact mechanical
Operating frequency rated value 50...60Hz
Number of NC contacts for auxiliary contacts 1
Number of NO contacts for auxiliary contacts 1
Number of CO contacts for auxiliary contacts 1
Operating current at AC-15
● at 24 V rated value
6A
● at 125 V rated value
6A
● at 240 V rated value
6A
● at 400 V rated value
4A
Operating current at DC-13
● at 24 V rated value
3A
● at 125 V rated value
0.55A
● at 250 V rated value
0.27A
● at 400 V rated value
0.12A
Design of the interface for safety-related
communication
without
Enclosure
Design of the housing block, wide
Material of the enclosure metal
Coating of the enclosure cathodic immersion coating
3SE5122-0CH82 Subject to change without notice
Page 2/
6
09/12/2019 © Copyright Siemens