Data Sheet
Product component front ring No
Holder
Material of the holder Plastic
General technical data
Product function
● EMERGENCY OFF function
Yes
● EMERGENCY STOP function
Yes
Protection class IP IP65
Operating frequency maximum 10001/h
Mechanical service life (switching cycles)
● typical
300000
Reference code acc. to DIN 40719 extended
according to IEC 204-2 acc. to IEC 750
S
Reference code acc. to DIN EN 81346-2 S
Reference code acc. to DIN EN 61346-2 S
Connections/Terminals
Tightening torque of the screws in the bracket 0.4N·m
Safety related data
B10 value
● with high demand rate acc. to SN 31920
100000
Proportion of dangerous failures
● with low demand rate acc. to SN 31920
20%
● with high demand rate acc. to SN 31920
20%
Failure rate [FIT]
● with low demand rate acc. to SN 31920
100FIT
T1 value for proof test interval or service life acc. to
IEC 61508
20y
Ambient conditions
Ambient temperature
● during operation
-25...+70°C
● during storage
-40...+80°C
Environmental category during operation acc. to IEC
60721
3K6
Installation/ mounting/ dimensions
Mounting type front mounting
Shape of the installation opening round
Mounting diameter 16mm
Mounting height 21mm
Installation width 28.5mm
Installation depth 50mm
3SB2000-1AC01 Subject to change without notice
Page 2/
3
09/12/2019 © Copyright Siemens