Data Sheet

● range changeover using
Changeover switch on device
● input voltage built-in
T 6.3 (not accessible)
Connections input spring-loaded terminal connection input (0.2 ... 2.5
mm2)/ diagnosis (0.14 ... 1.5 mm2)
Outputs:
output
● DC-voltage controlled floating according to AS-
Interface spezification
yes
● voltage rated value Ua rated DC
30 V
● tolerance total DC
V 29.5...31.6
● rated current Ia rated
8 A
● residual ripple peak-to-peak ( 0-10 kHz, AS-
i+/AS-i- ) max
mV 300
● spikes peak-to-peak ( 10-500 kHz, AS-i+/AS-i- )
max
mV 50
Connections Output spring-loaded terminal connection output (0.2 ... 2.5
mm²)/ diagnosis (0.14 ... 1.5 mm²)
Efficiency/ heat loss:
Efficiency at Ua rated, Ia rated % 87
Protective and monitoring functions:
Output overvoltage protection yes (< 35V)
Current limitation from min. 8.5 A
Short-circuit protection yes
Safety related data:
protection class ( EN 60 950/IEC 950 ) I
Electrical isolation primary/secondary SELV according to EN 60 950 and EN 50 178
Protection class IP IP20
Electromagnetic compatibility:
electromagnetic compatibility (EMC)
● interference immunity
EN 61 000-6-2, EN 61 000-4-2/-3/-4/-5/-11
● emitted interference
class B according to EN 55 022, IEC 61 000-6-3
Ambient conditions:
Ambient temperature
● during operation
°C -10...+70
● during storage
°C -25...+80
humidity rating climatic class DIN 50010, relative humidity max.
100% without condensation
Mounting type fixing on standard mounting rail DIN EN 59 022-35 x
7.5 mm snap-on
Width mm 120
Height mm 125
3RX9503-0BA00 Subject to change without notice
Page 2/
4
09/13/2019 © Copyright Siemens