Datasheet
● at 60 °C to power-up
21W
Control circuit/ Control
Type of voltage of the control supply voltage AC
Control supply voltage at AC
● at 50 Hz
110...250V
● at 60 Hz
110...250V
Relative negative tolerance of the control supply
voltage at AC at 50 Hz
-15%
Relative positive tolerance of the control supply
voltage at AC at 50 Hz
10%
Relative negative tolerance of the control supply
voltage at AC at 60 Hz
-15%
Relative positive tolerance of the control supply
voltage at AC at 60 Hz
10%
Control supply voltage frequency 50...60Hz
Relative negative tolerance of the control supply
voltage frequency
-10%
Relative positive tolerance of the control supply
voltage frequency
10%
Control supply current in standby mode rated value 30mA
Holding current in the by-pass mode operating rated
value
75mA
Starting current at close of by-pass contact maximum 0.17A
Inrush current peak at connect of control supply
voltage maximum
12.2A
Duration of inrush current peak at connect of control
supply voltage
2.2ms
Design of the overvoltage protection Varistor
Design of short-circuit protection for control circuit 4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1
miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker
(Icu= 300 A); Is not part of scope of supply
Inputs/ Outputs
Number of digital inputs 1
Number of inputs for thermistor connection 0
Number of digital outputs 3
● not parameterizable
2
Digital output version 2 normally-open contacts (NO) / 1 changeover contact (CO)
Number of analog outputs 1
Switching capacity current of the relay outputs
● at AC-15 at 250 V rated value
3A
● at DC-13 at 24 V rated value
1A
Installation/ mounting/ dimensions
Mounting position with vertical mounting surface +/-90° rotatable, with vertical
mounting surface +/- 22.5° tiltable to the front and back
3RW5217-1AC14 Subject to change without notice
Page 4/
9