Data Sheet
Relative negative tolerance of the control supply
voltage frequency
% -10
Relative positive tolerance of the control supply
voltage frequency
% 10
Control supply voltage 1 at AC
● at 50 Hz rated value
V 115
● at 60 Hz rated value
V 115
Relative negative tolerance of the control supply
voltage at AC at 50 Hz
% -15
Relative positive tolerance of the control supply
voltage at AC at 50 Hz
% 10
Relative negative tolerance of the control supply
voltage at AC at 60 Hz
% -15
Relative positive tolerance of the control supply
voltage at AC at 60 Hz
% 10
Display version for fault signal Display
Mechanical data
Width mm 170
(height) mm 200
Depth mm 270
(mounting type) screw fixing
(mounting position) with vertical mounting surface +/-90° rotatable, with
vertical mounting surface +/- 22.5° tiltable to the front
and back
Required spacing with side-by-side mounting
● upwards
mm 100
● at the side
mm 5
● downwards
mm 75
Wire length maximum m 500
Number of poles for main current circuit 3
Connections/Terminals
Type of electrical connection
● for main current circuit
busbar connection
● for auxiliary and control current circuit
screw-type terminals
Number of NC contacts for auxiliary contacts 0
Number of NO contacts for auxiliary contacts 3
Number of CO contacts for auxiliary contacts 1
Type of connectable conductor cross-sections for
main contacts for box terminal using the front
clamping point
● finely stranded with core end processing
16 ... 70 mm²
● finely stranded without core end processing
16 ... 70 mm²
● stranded
16 ... 70 mm²
3RW44 36-6BC36 Subject to change without notice
Page 3/
7
09/13/2019 © Copyright Siemens