Data Sheet

Power Electronics
Product designation Soft starter
Operating current
● at 40 °C rated value
A 162
● at 50 °C rated value
A 145
● at 60 °C rated value
A 125
Operating current for three-phase motors at inside-
delta circuit
● at 40 °C rated value
A 281
● at 50 °C rated value
A 251
● at 60 °C rated value
A 217
Mechanical power output for three-phase motors
● at 400 V
— at standard circuit at 40 °C rated value
W 90000
— at inside-delta circuit at 40 °C rated value
W 160000
● at 500 V
— at standard circuit at 40 °C rated value
W 110000
— at inside-delta circuit at 40 °C rated value
W 200000
● at 690 V at standard circuit at 40 °C rated value
W 160000
Operating frequency rated value Hz 50...60
Relative negative tolerance of the operating
frequency
% -10
Relative positive tolerance of the operating frequency % 10
Operating voltage at standard circuit rated value V 400...690
Relative negative tolerance of the operating voltage
at standard circuit
% -15
Relative positive tolerance of the operating voltage at
standard circuit
% 10
Operating voltage at inside-delta circuit rated value V 400...600
Relative negative tolerance of the operating voltage
at inside-delta circuit
% -15
Relative positive tolerance of the operating voltage at
inside-delta circuit
% 10
Minimum load [%] % 8
Adjustable motor current for motor overload
protection minimum rated value
A 32
Continuous operating current [% of Ie] at 40 °C % 115
Power loss [W] at operating current at 40 °C during
operation typical
W 95
Control electronics
Type of voltage of the control supply voltage AC
Control supply voltage frequency 1 rated value Hz 50
Control supply voltage frequency 2 rated value Hz 60
3RW44 36-6BC36 Subject to change without notice
Page 2/
7
09/13/2019 © Copyright Siemens