User Manual
Configuration
11.1 Configuration in general
SIRIUS 3RW30 / 3RW40
Manual, 10/2010, 535199502000 DS 03
79
Heavy-duty starting (CLASS 20)
applications
3RW30 3RW40 3RW44
Agitator - x +
Extruder - x +
Turning machine - x +
Milling machine - x +
+ Recommended soft starter
x Possible soft starter
Ultra-heavy-duty starting (CLASS 30)
applications
3RW30 3RW40 3RW44
Large fan
2)
- - +
Circular saw / band saw - - +
Centrifuge - - +
Mill - - +
Crusher - - +
+ Recommended soft starter
2) Large fan: Mass inertia (centrifugal mass) of fan >= 10 x mass inertia of motor
Soft starter functions 3RW30 3RW40 3RW44
Soft start function + + +
Soft stop function - + +
Integrated intrinsic device protection - + +
Integrated electronic motor overload protection - + +
Settable current limiting - + +
Special pump stop function - - +
Braking in ramp-down - - +
Settable breakaway torque - - +
Communication via PROFIBUS (optional) - - +
External operation and indication display (optional) - - +
Soft Starter ES parameterization software - - +
Special functions, e.g. measured values, display
languages etc.
- - +
Motor overload protection acc. to ATEX - + -
+ Recommended soft starter