8.5 Soft starter assembly with type of coordination 2
The SIRIUS 3RW40 soft starter has internal protection to prevent overloading of the
thyristors. The SIRIUS 3RW30 soft starter has no internal protection to prevent overloading
of the thyristors. The soft starter must always be dimensioned according to the duration of
the startup process and the desired starting frequency. If the feeder of the SIRIUS 3RW30 or
3RW40 soft starter is assembled accordingly with the feeder components recommended in
chapter Technical data (Page 127) (e.g. motor starter protec
tor or LV HRC fuse), type of
coor
dination 1 is achieved. In order to achieve type of coordination 2, all thyristors must be
additionally protected against short-circuits by means of special semiconductor fuses (e.g.
SIEMENS SITOR). A short-circuit can occur, for instance, as a result of a defect in the motor
windings or in the motor's power supply cable.
L2
L1
L3
PE
3/N/PE~ 50 Hz 400 V
4
4
)
0
8
: 8 9
:
9
8
: 8 9
:
9
Figure 8-3 Block diagram of a feeder with semiconductor fuses
Note