User Manual
Functions
5.5 Functions of the inputs
SIRIUS 3RW30 / 3RW40
44 Manual, 10/2010, 535199502000 DS 03
For recommended circuits, e.g. control by means of pushbuttons, contactor contacts, or a
PLC, refer to chapter Typical circuit diagrams (Page 175).
5.5.3 Thermistor input / connection on 3RW40 2 to 3RW40 4
24 V AC/DC rated control voltage
After removing the copper jumper between T11/21 and T22, you can connect and evaluate
either a Klixon thermistor integrated in the motor winding (at terminal T11/T21-T22) or a type
A PTC (at terminal T11/T21-T12).
ϑ
T11/T21 T12 T22
ϑ
ϑ
T22T12
ϑ
T11/T21
Klixon Type A PTC