User Manual

Functions
5.4 Functions of the RESET buttons
SIRIUS 3RW30 / 3RW40
Manual, 10/2010, 535199502000 DS 03
41
5.4.2.4 AUTO RESET
AUTO RESET (AUTO LED = yellow)
If you set the RESET mode to AUTO, a fault is automatically reset as follows:
If the motor overload protection function trips: after 5 minutes
If the intrinsic device protection function trips:
- after 30 seconds upon overload of the thyristors,
- after 60 seconds upon overload of the bypasses
WARNING
Automatic restart
Can result in death, serious injury, or property damage.
The automatic RESET mode (AUTO RESET) must not be used in applications where
there is a risk of serious injury to persons or substantial damage to property if the motor
starts up again unexpectedly. The start command (e.g. issued by a contact or the PLC)
must be reset prior to issuing a RESET command because the motor attempts to restart
again automatically following this RESET command if a start command is still present.
This particularly applies if the motor protection has tripped. For safety reasons, you are
advised to integrate the group fault output (terminals 95 and 96) in the controller.
5.4.2.5 Acknowledging faults
For information about whether or not faults can be acknowledged as well as the
corresponding LED and output contact states, refer to chapter Diagnostics and fault signals
(Page 48).
5.4.3 Other functions of the RESET button
5.4.3.1 Motor protection trip test
You initiate a motor overload trip by pressing the RESET / TEST button for longer than five
seconds. The SIRIUS 3RW40 soft starter is tripped by the fault signal at the OVERLOAD
LED, the FAILURE / OVERLOAD contact 95-98 closes, and the motor that is connected and
running is switched off.
RESET / TEST button on the 3RW40 2,
3RW40 3, and 3RW40 4
RESET / TEST button on the 3RW40 5 and
3RW40 7