5.1 Start modes
SIRIUS 3RW30 / 3RW40
Manual, 10/2010, 535199502000 DS 03
31
Ramp-up detection (3RW40 only)
The SIRIUS 3RW40 soft starter is equipped with an integrated ramp-up detection function. If
it detects a motor startup, the motor voltage is immediately increased to 100 % of the mains
voltage. The internal bypass contacts close and the thyristors are bridged.
0RWRUFXUUHQW
,
,
'LUHFW
RQOLQH
VWDUWLQJ
PRWRU
,
6RIWVWDUWHU
DGMXVWDEOHFXUUHQW
OLPLWYDOXH
%HJLQQLQJGHWHU
PLQHGE\VSHFLILHG
VWDUWLQJPRGHLQWKLV
FDVHYROWDJHUDPS
,
H0RWRU
Q
H0RWRU
0RWRUVSHHG
Q
0RWRUUXQXS
UHFRJQL]HG
E\SDVVFRQWDFWV
FORVH
Figure 5-4 Current limiting with soft starter
Typical applications for current limiting
Current limiting is used for applications with large centrifugal masses (mass inertias) and
therefore longer ramp-up times, e.g. fans, circular saws etc.