User Manual
Typical circuit diagrams
15.9 Emergency stop
SIRIUS 3RW30 / 3RW40
198 Manual, 10/2010, 535199502000 DS 03
(1) For the permissible values for the main and control voltage (dependent on the MLFB),
refer to chapter Technical data (Page 127) .
WARNING
(2) Automatic restart. Can result in death, serious injury, or property damage.
- If the 3TK28 is reset
Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to
chapter 3RW30: LEDs and troubleshooting (Page 48)) are automatically reset when the
system returns to normal.
An automatic r
estart is initiated and the 3RW restarted if a start command is present at the
input.
If you do not want the motor to start automatically, you must integrate suitable additional
components, e.g. phase failure or load monitoring devices, into the control and main
circuits.
(3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type
of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter
Technical data (Page 127)
15.9.2 3RW40 2 to 3RW40 4 emergency stop and 3TK2823 safety relay
(PHUJHQF\
VWRS
/b9b'&
2Q
7.5(6(7
4 4
0
6
6
4
4
7.&%
$ < < <
<$<<
Figure 15-25 Wiring of the emergency stop control circuit and the 3TK28 safety relay