User Manual

Typical circuit diagrams
15.5 Control by PLC
SIRIUS 3RW30 / 3RW40
Manual, 10/2010, 535199502000 DS 03
187
(1) For the permissible values for the main and control voltage (dependent on the MLFB),
refer to chapter Technical data (Page 127) .
WARNING
(2) Automatic restart.
Can result in death, serious injury, or property damage.
The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a
RESET command because the motor attempts to restart again automatically following this
RESET command if a start command is still present. This particularly applies if the motor
protection has tripped. For safety reasons, you are advised to integrate the group fault
output (terminals 95 and 96) in the controller.
(3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type
of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter
Technical data (Page 127)
For the optio
nal thermistor motor protection evaluation, refer to Typical
circuit for the optional
thermi
stor motor protection eval
uation (Page 175).