User Manual
Commissioning
12.10 RESET MODE and functions of the RESET / TEST button
SIRIUS 3RW30 / 3RW40
122 Manual, 10/2010, 535199502000 DS 03
Remote RESET with module for RESET (AUTO LED = off)
You can perform a remote RESET (the RESET MODE set on the starter is MANUAL
RESET) by controlling the optional module for RESET (3RU1900-2A).
12.10.2.4 AUTO RESET
AUTO RESET (AUTO LED = yellow)
If you set the RESET mode to AUTO, a fault is automatically reset.
Note
For information about whether or not faults can be acknowledged, as well as the recovery
time and the corresponding LED and output contact states, refer to chapter Diagnostics and
fault signal
s (Page 48).
WARNING
Automatic restart
Can result in death, serious injury, or property damage.
The automatic RESET mode (AUTO RESET) must not be used in applications where there
is a risk of serious injury to persons or substantial damage to property if the motor starts up
again unexpectedly. The start command (e.g. issued by a contact or the PLC) must be
reset prior to issuing a RESET command because the motor attempts to restart again
automatically following this RESET command if a start command is still present. This
particularly applies if the motor protection has tripped. For safety reasons, you are advised
to integrate the group fault output on the 3RW40 (terminals 95 and 96), or the signaling
contact of the motor or miniature circuit breaker on all devices, in the controller.