Soft starters SIRIUS 3RW30 / 3RW40 Manual • 10/2010 Industrial Controls Answers for industry.
Industrial Controls Soft starters SIRIUS 3RW30 / 3RW40 Introduction 1 Safety information 2 Product description 3 Product combinations 4 Functions 5 Application planning 6 Installation 7 Installation / mounting 8 Connecting 9 Manual Operation 10 Configuration 11 Commissioning 12 Technical data 13 Dimension drawings 14 Typical circuit diagrams 15 Accessories 16 Appendix 10/2010 535199502000 DS 03 A
Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
Table of contents 1 Introduction.............................................................................................................................................. 11 1.1 2 3 4 Safety information.................................................................................................................................... 13 2.1 Before commencing work: Isolating the equipment from the supply system and ensuring that it cannot be reconnected...............................................
Table of contents 6 5.4.3.1 5.4.3.2 5.4.4 Motor protection trip test ............................................................................................................. 41 Reparameterizing the ON / RUN output contact......................................................................... 42 Reset options for fault acknowledgement ................................................................................... 42 5.5 5.5.1 5.5.2 5.5.3 Functions of the inputs ...............................
Table of contents 12 11.2 11.2.1 11.2.2 Startup class ................................................................................................................................81 Application examples for normal starting (CLASS 10) with 3RW30 and 3RW40........................82 Application examples for heavy-duty starting (CLASS 20): 3RW40 only ....................................83 11.3 ON time and switching frequency ...............................................................................
Table of contents 12.9.1 12.9.2 12.9.3 Functions of the BYPASSED and ON / RUN outputs............................................................... 115 Parameterizing the 3RW40 outputs .......................................................................................... 116 Function of the FAILURE / OVERLOAD output ........................................................................ 118 12.10 RESET MODE and functions of the RESET / TEST button ...................................................
Table of contents 14 15 13.2.16 13.2.17 13.2.18 13.2.19 13.2.20 13.2.21 13.2.22 13.2.23 13.2.24 13.2.25 13.2.26 13.2.27 13.2.28 3RW40 55, 56, 73, 74, 75, 76 power electronics.......................................................................158 3RW40 2., 3., 4. main conductor cross-sections .......................................................................159 3RW40 5., 7. main conductor cross-sections ............................................................................160 3RW40 ..
Table of contents 15.10.2 3RW40 and contactor for emergency starting .......................................................................... 203 15.11 15.11.1 15.11.2 15.11.3 16 A Dahlander / multispeed motor ................................................................................................... 205 3RW30 and Dahlander motor starting ...................................................................................... 205 3RW40 2 to 3RW40 4 and Dahlander motor starting ...................
Introduction 1.1 1 Important notes Purpose of the manual This manual contains fundamental information and practical tips for using SIRIUS soft starters. The SIRIUS 3RW30 and 3RW40 soft starters are electronic motor control devices that facilitate optimal starting and stopping three-phase induction motors. The manual describes all of the functions of the SIRIUS 3RW30 and 3RW40 soft starters.
Introduction 1.1 Important notes Orientation aids The manual contains various features supporting quick access to specific information: ● At the beginning of the manual you will find a table of contents. ● A comprehensive index at the end of the manual allows quick access to information on specific subjects. Continuously updated information Your regional contact for low-voltage switchgear with communications capability will be happy to help you with any queries you have regarding the soft starters.
Safety information 2.1 2 Before commencing work: Isolating the equipment from the supply system and ensuring that it cannot be reconnected. DANGER Hazardous voltage Will cause death or serious injury. • Disconnect the system and all devices from the power supply before starting work. • Secure against switching on again. • Verify that the equipment is not live. • Ground and short-circuit. • Erect barriers around or cover adjacent live parts. DANGER Hazardous voltage Will cause death or serious injury.
Safety information 2.2 Five safety rules for work in or on electrical systems 2.2 Five safety rules for work in or on electrical systems A set of rules, which are summarized in DIN VDE 0105 as the "five safety rules", are defined for work in or on electrical systems as a preventative measure against electrical accidents: 1. Isolate 2. Secure against switching on again 3. Verify that the equipment is not live 4. Ground and short-circuit 5.
Product description 3.1 3 Fields of application Soft starters are used to start three-phase induction motors with reduced torque and reduced starting current. SIRIUS soft starter family The SIEMENS SIRIUS soft starter family comprises three different versions with different functionalities and prices. 3RW30 and 3RW40 Simple or standard applications are covered by the SIRIUS 3RW30 and 3RW40 soft starters and are described in this manual.
Product description 3.2 Basic physical principles of a three-phase induction motor 3.2 Basic physical principles of a three-phase induction motor SIRIUS soft starters are used to reduce the current and torque of a three-phase induction motor during the startup process. 3.2.1 Three-phase induction motor Fields of application Three-phase induction motors are used in a wide range of applications in commerce, industry, and trade owing to their simple, robust design and their minimal maintenance.
Product description 3.2 Basic physical principles of a three-phase induction motor Starting torque The starting torque and the breakdown torque can usually be assumed to be between two and four times the rated torque. From the point of view of the load machine, this means that the starting and acceleration forces exert a higher mechanical load on the machine and the product being conveyed compared to nominal operation.
Product description 3.3 Functional principle of the SIRIUS 3RW30 and 3RW40 soft starters 3.3 Functional principle of the SIRIUS 3RW30 and 3RW40 soft starters The SIRIUS 3RW30 and 3RW40 soft starters have two antiparallel thyristors in two out of the three phases. One thyristor for the positive half-wave and one for the negative half-wave is provided in each phase (refer to Fig. "Phase angle control and schematic diagram of a twophase controlled soft starter with integral bypass contacts").
Product description 3.
Product description 3.3 Functional principle of the SIRIUS 3RW30 and 3RW40 soft starters Bypass mode Once the motor has been started up correctly, the thyristors are subject to fully advanced control, meaning that the whole mains voltage is applied to the motor terminals. As the motor voltage does not have to be controlled during operation, the thyristors are bridged by integral bypass contacts that are rated for AC1 current.
Product description 3.3 Functional principle of the SIRIUS 3RW30 and 3RW40 soft starters The occurrence of DC components, caused by the phase angle and the overlapping phase currents, is a negative physical effect of two-phase control during the startup process that can mean a louder noise is produced by the motor. The "polarity balancing" control principle was developed and patented by SIEMENS to prevent these DC components during starting.
Product description 3.3 Functional principle of the SIRIUS 3RW30 and 3RW40 soft starters ,$ ,$ WV Figure 3-8 ,$ WV WV Starting current asymmetry Note If wye-delta starters are exchanged for soft starters in an existing system, you should check the fuse ratings in the feeder in order to avoid false tripping. This is particularly important in connection with heavy-duty starting or if the fuse that is installed has already been operated close to the thermal tripping limit with the wye-delta assembly.
Product description 3.3 Functional principle of the SIRIUS 3RW30 and 3RW40 soft starters 3.3.3 Applications and use Applications and selection criteria The SIRIUS 3RW30 and 3RW40 soft starters represent a good alternative to direct or wyedelta starters.
Product description 3.4 Comparison of device functions 3.4 Comparison of device functions 5DWHG FXUUHQW DW r& b r& 5DWHG RSHUDWLRQDO YROWDJH 0RWRU UDWLQJ DW 9b b 9 ವ6WDQGDUG FRQQHFWLRQ ವ,QVLGH GHOWD FLUFXLW $PELHQW WHPSHUDWXUH 6RIW VWDUW VRIW VWRS 9ROWDJH UDPS 6WDUWLQJ VWRSSLQJ YROWDJH 5DPS XS DQG UDPS GRZQ WLPH 7RUTXH FRQWURO 6WDUWLQJ VWRSSLQJ WRUTXH 7RUTXH OLPLWLQJ 5DPS WLPH ,QWHJUDWHG MXPSHU FRQWDFW V\VWHP ,QWULQVLF GHYLFH SURWHFWLRQ 0RWRU RYHUORDG SURWHFWLRQ 7KHUPLVWRU PRWRU SURWHFWLRQ
Product combinations 4.1 4 SIRIUS modular system Switching, protecting, and starting motors In order to simplify the assembly of load feeders, the SIRIUS modular system offers standard components that are optimally harmonized and are easy to combine. Just 7 sizes cover the entire performance range up to 250 kW / 300 hp. The individual switching devices can be assembled to form complete load feeders, either using link modules or by mounting directly. For a selection of matching device combinations, e.g.
Product combinations 4.1 SIRIUS modular system 6,5,86 PRWRU VWDUWHU SURWHFWRUV 59 6 59 6 6(17521 FLUFXLW EUHDNHUV 59 6 59 6 9/ 9/ 9/ 9/ 9/ 9/ 6,5,86 FRQWDFWRUV 57 6 57 6 57 6 57 6 57 6 5% 6 5% 6 5% 6 5: 6 5: 6 5: 6 57 6 57 6 6,5,86 RYHUORDG UHOD\V 5% 6 5% 6 5% 6 6 6,5,86 VRIW VWDUWHUV 5: 6 Figure 4-
5 Functions 5.1 Start modes You can choose between different startup functions reflecting the wide range of applications and functionality of the SIRIUS 3RW30 and 3RW40 soft starters. The motor start can be optimally adapted to each particular application. 5.1.1 Voltage ramp The SIRIUS 3RW30 and 3RW40 soft starters achieve soft starting by means of a voltage ramp. The motor terminal voltage is increased from a parameterizable starting voltage up to the mains voltage within a definable ramp-up time.
Functions 5.1 Start modes The SIRIUS 3RW40 soft starter has intrinsic device protection, current limiting, and ramp-up detection functions. These functions do not form part of the SIRIUS 3RW30 soft starter. CAUTION Risk of property damage When using the 3RW30: Make sure the selected ramp time is longer than the actual motor ramp-up time. If not, the SIRIUS 3RW30 may be damaged because the internal bypass contacts close when the set ramp time elapses.
Functions 5.
Functions 5.1 Start modes 5.1.2 Current limiting and ramp-up detection (3RW40 only) The SIRIUS 3RW40 soft starter measures the phase current (motor current) continuously with the help of integrated current transformers. The motor current that flows during the startup process can be actively limited by means of the soft starter. The current limiting function takes priority over the voltage ramp function.
Functions 5.1 Start modes Ramp-up detection (3RW40 only) The SIRIUS 3RW40 soft starter is equipped with an integrated ramp-up detection function. If it detects a motor startup, the motor voltage is immediately increased to 100 % of the mains voltage. The internal bypass contacts close and the thyristors are bridged. 0RWRU FXUUHQW , ,'LUHFW RQ OLQH VWDUWLQJ PRWRU ,6RIW VWDUWHU DGMXVWDEOH FXUUHQW OLPLW YDOXH %HJLQQLQJ GHWHU PLQHG E\ VSHFLILHG VWDUWLQJ PRGH LQ WKLV FDVH YROWDJH UDPS 0RWRU UXQ XS UHFRJQL
Functions 5.2 Stop modes 5.2 Stop modes You can choose between different stop modes reflecting the wide range of applications for SIRIUS soft starters. The motor stop can be optimally adapted to each particular application. If a start command is issued during the stop process, the process is interrupted and the motor is started again with the set start mode.
Functions 5.2 Stop modes 5.2.2 Soft stop (3RW40 only) In "soft stop" mode, the natural stop process of the load is decelerated. The function is used when the load must be prevented from stopping abruptly. This is typically the case in applications with a low mass inertia or a high counter-torque. Ramp-down time The "Ramp-down time" potentiometer on the soft starter allows you to specify how long power should still be supplied to the motor after the ON command is removed.
Functions 5.3 Motor protection / intrinsic device protection (3RW40 only) 5.3 Motor protection / intrinsic device protection (3RW40 only) NOTICE If the soft starter is disconnected because the motor overload protection or the intrinsic device protection trips, you must wait a defined cooling time (recovery time) prior to acknowledging the fault or starting the motor again.
Functions 5.3 Motor protection / intrinsic device protection (3RW40 only) / / 1 / ) 21 57 4 5: $ $ ,1 5: 0 a Figure 5-5 $ 4 $ 3RW40 wiring fault / / 1 / 21 4 , ! 59 5: $ $ ,1 5: 0 a Figure 5-6 4 ' 8 ' 3RW40 wiring fault with 3RV For further information, refer to the operating instructions, Order No. 3ZX1012-0RW40-1CA1 (http://support.automation.siemens.com/WW/view/de/22809303). WARNING Danger of death or serious injury.
Functions 5.3 Motor protection / intrinsic device protection (3RW40 only) Trip class (electronic overload protection) The trip class (CLASS) specifies the maximum time within which a protective device must trip from a cold state at 7.2 x the rated operational current (motor protection to IEC 60947). The tripping characteristics represent this time as a function of the tripping current (refer to chapter Motor protection tripping characteristics for 3RW40 (with symmetry) (Page 168)).
Functions 5.3 Motor protection / intrinsic device protection (3RW40 only) Recovery time (thermistor motor protection) If the thermistor motor protection is tripped, the soft starter cannot be restarted until the sensor installed in the motor has cooled down. The recovery time varies according to the temperature state of the sensor. 5.3.
Functions 5.4 Functions of the RESET buttons 5.4 Functions of the RESET buttons 5.4.1 SIRIUS 3RW40 2, 3RW40 3, and 3RW40 4 soft starters 5.4.1.1 RESET MODE button and LED By pressing the RESET MODE button, you define the reset procedure in case of a fault. This is indicated by the RESET MODE LED. Yellow = AUTO Off = MANUAL Green = REMOTE Note On the SIRIUS 3RW40 2.
Functions 5.4 Functions of the RESET buttons 5.4.1.3 Remote RESET Remote RESET (RESET MODE LED = green) You can reset a fault signal by disconnecting the control supply voltage for >1.5 s. 1 / / / 5(6(7 21 2)) 8V $ $ ! V W 5.4.1.
Functions 5.4 Functions of the RESET buttons 5.4.2 SIRIUS 3RW40 5 and 3RW40 7 soft starters 5.4.2.1 RESET MODE button and AUTO LED By pressing the RESET MODE button, you define the reset procedure in case of a fault. This is indicated by the AUTO LED. Yellow = AUTO Off = MANUAL (REMOTE) 5.4.2.2 Manual RESET Manual RESET with the RESET / TEST button (AUTO LED = off) You can reset a fault by pressing the RESET / TEST button. 5.4.2.
Functions 5.4 Functions of the RESET buttons 5.4.2.4 AUTO RESET AUTO RESET (AUTO LED = yellow) If you set the RESET mode to AUTO, a fault is automatically reset as follows: ● If the motor overload protection function trips: after 5 minutes ● If the intrinsic device protection function trips: - after 30 seconds upon overload of the thyristors, - after 60 seconds upon overload of the bypasses WARNING Automatic restart Can result in death, serious injury, or property damage.
Functions 5.4 Functions of the RESET buttons 5.4.3.2 Reparameterizing the ON / RUN output contact For information about reparameterizing the output with the RESET / TEST button, refer to chapter Parameterizing the 3RW40 outputs (Page 116) . 5.4.
Functions 5.5 Functions of the inputs 5.5 Functions of the inputs 5.5.1 Start input (terminal 1) on 3RW30 and 3RW40 2 to 3RW40 4 Rated control voltage is present at terminal A1 / A2: The startup process of the soft starter begins when a signal is present at terminal 1 (IN). The starter operates until the signal is removed again. If a ramp-down time is parameterized (3RW40 only), a soft stop starts as soon as the signal is removed.
Functions 5.5 Functions of the inputs For recommended circuits, e.g. control by means of pushbuttons, contactor contacts, or a PLC, refer to chapter Typical circuit diagrams (Page 175). 5.5.3 Thermistor input / connection on 3RW40 2 to 3RW40 4 24 V AC/DC rated control voltage After removing the copper jumper between T11/21 and T22, you can connect and evaluate either a Klixon thermistor integrated in the motor winding (at terminal T11/T21-T22) or a type A PTC (at terminal T11/T21-T12).
Functions 5.6 Functions of the outputs 5.6 Functions of the outputs 5.6.1 3RW30: Output terminal 13 / 14 ON The potential-free output contact at terminal 13/14 (ON) closes if a signal is present at terminal 1 (IN); it remains closed until the start command is removed. The output can be used, for instance, to control a line contactor connected upstream or to implement latching if you selected pushbutton control. For recommended circuits, refer to chapter Typical circuit diagrams (Page 175).
Functions 5.6 Functions of the outputs RUN The RUN output remains closed as long as the motor is controlled by the soft starter, in other words during the startup phase, in bypass mode, and during the soft stop (if set). This output function can be used, for instance, if a line contactor connected upstream must be controlled by the soft starter, especially if the soft stop function is set. BYPASSED The BYPASSED function can be used, for instance, to indicate that the motor has started up successfully.
Functions 5.6 Functions of the outputs 5.6.3 3RW40: Group fault output at terminal 95 / 96 / 98 OVERLOAD / FAILURE If there is no rated control voltage or if a failure occurs, the potential-free FAILURE / OVERLOAD output is switched. For recommended circuits, refer to chapter Typical circuit diagrams (Page 175). For a state diagram of the contacts in the various fault and operating states, refer to chapter Diagnostics and fault signals (Page 48).
Functions 5.7 Diagnostics and fault signals 5.7 Diagnostics and fault signals 5.7.1 3RW30: LEDs and troubleshooting /('V RQ 5: 6RIW VWDUWHU '(9,&( UG JQ \OZ 5: $X[LOLDU\ FRQWDFW 67$7( %<3$66(' )$,/85( JQ UG 21 8V 2SHUDWLQJ VWDWH ,1 2II JQ 6WDUW JQ %\SDVVHG JQ JQ JQ )DXOW ,PSHUPLVVLEOH HOHFWURQLFV VXSSO\ YROWDJH %\SDVV RYHUORDG UG 0LVVLQJ ORDG YROWDJH 3KDVH IDLOXUH PLVVLQJ ORDG 'HYLFH IDXOW \OZ UG JQ UG UG UG /('V 2II 21 )ODVKLQ
Functions 5.7 Diagnostics and fault signals For notes on troubleshooting, refer to the table below. Fault Cause Remedy Impermissible electronics supply voltage The control supply voltage does not correspond to the soft starter's rated voltage. Check the control supply voltage; an incorrect control supply voltage could be caused by a power failure or a voltage dip. Bypass overload A current > 3.5 x Ie of the soft starter occurs for > 60 ms in bypass mode (e.g. because the motor is blocked).
Functions 5.7 Diagnostics and fault signals 5.7.2 3RW40: LEDs and troubleshooting /(' VWDWXVHV 5: $X[LOLDU\ FRQWDFWV 0RWRU SURWHFWLRQ 6RIW VWDUWHU 67$7( 5(6(7 02'( %<3$66(' 29(5/2$' $872 '(9,&( )$,/85( UG \OZ JQ UG JQ \OZ JQ UG 5: 21 581 )$,/85( %<3$66(' 29(5/2$' 8V 2SHUDWLQJ VWDWH ,1 2II JQ 6WDUW JQ JQ %\SDVVHG JQ JQ 6WRS JQ JQ :DUQLQJ ,H FODVV VHWWLQJ LPSHUPLVVLEOH JQ 6WDUW LQKLELWHG GHYLFH WRR ZDUP FRROLQJ WLP
Functions 5.7 Diagnostics and fault signals WARNING Automatic restart Can result in death, serious injury, or property damage. The automatic RESET mode (AUTO RESET) must not be used in applications where there is a risk of serious injury to persons or substantial damage to property if the motor starts up again unexpectedly. The start command (e.g.
Functions 5.7 Diagnostics and fault signals Fault Cause Remedy Impermissible electronics supply voltage: The control supply voltage does not correspond to the soft starter's rated voltage. Check the control supply voltage; could be caused by a power failure, voltage dip, or incorrect control supply voltage. Use a stabilized power supply unit if due to mains fluctuations.
Functions 5.7 Diagnostics and fault signals Fault Device fault SIRIUS 3RW30 / 3RW40 Manual, 10/2010, 535199502000 DS 03 Cause Remedy Cause 3: Motor phase T1 / T2 / T3 is not connected. Connect the motor properly (e.g. jumpers in the motor terminal box, repair switch closed etc.) Soft starter defective. Contact your SIEMENS partner or Technical Assistance.
Functions 5.
Application planning 6.1 Application examples 6.1.1 Roller conveyor application 6 Using the 3RW30 with roller conveyors Roller conveyors are employed, for example, in parcel distribution systems for transporting parcels to and from individual workstations. For this purpose, the direction of rotation of the 11 kW / 15 hp motor that is used has to be adjustable in order for the conveyor to work in both directions.
Application planning 6.1 Application examples 6.1.2 Hydraulic pump application Using the 3RW40 with hydraulic pumps The SIRIUS 3RW40 is optimally suited for soft starting and stopping of hydraulic pumps. With a rating of 200 kW / 250 hp, this soft starter is used, for example, in the production of sheet parts to drive the presses.
7 Installation 7.1 Installing the soft starter 7.1.1 Unpacking CAUTION Do not lift the device by the cover in order to unpack it, especially sizes 3RW40 55 to 3RW40 76, because this could lead to damage. Permissible mounting position 3RW40 2 to 3RW40 4 (with optional additional fan) 3RW40 3RW40 5 to 3RW40 7 10° 10° 10° 10° Vertical mounting 90˚ 90˚ NSB00649 3RW30 NSB0_01897 7.1.
Installation 7.1 Installing the soft starter 7.1.3 Mounting dimensions, clearances, and assembly type The minimum clearances from other devices must be complied with to ensure unobstructed cooling as well as the free supply and discharge of air to and from the heat sink. E 11 3 5 a a 2 4 6 F Figure 7-1 Clearances from other devices MLFB a (mm) a (in) b (mm) b (in) c (mm) c (in) 3RW30 1./3RW30 2. 15 0.59 60 2.36 40 1.56 3RW30 3./3RW30 4 30 1.18 60 2.36 40 1.56 3RW40 2.
Installation 7.1 Installing the soft starter 7.1.4 Assembly type: Standalone assembly, side-by-side assembly, direct mounting Standalone assembly The term "standalone assembly" is used if the clearances a / b / c described in chapter Mounting dimensions, clearances, and assembly type (Page 58) are complied with.
Installation 7.1 Installing the soft starter The term "direct mounting" is used if the top clearance b described in chapter Mounting dimensions, clearances, and assembly type (Page 58) is not complied with, e.g. if the soft starter is mounted directly on a motor starter protector (e.g. 3RV2) using a link module (e.g. 3RV29). NOTICE The permissible switching frequency values can vary according to the selected assembly type.
Installation / mounting 8.1 8 General information General information A motor feeder comprises a disconnector, a contact, and a motor as a minimum. Line protection against short-circuits must be implemented, together with overload protection for the line and motor. Disconnector The isolating function with line protection against overload and short-circuits can be achieved with a motor starter protector or a fuse disconnector, for instance.
Installation / mounting 8.2 Five safety rules for work in or on electrical systems 8.2 Five safety rules for work in or on electrical systems A set of rules, which are summarized in DIN VDE 0105 as the "five safety rules", are defined for work in or on electrical systems as a preventative measure against electrical accidents: 1. Isolate 2. Secure against switching on again 3. Verify that the equipment is not live 4. Ground and short-circuit 5.
Installation / mounting 8.3 General feeder assembly (type of coordination 1) 8.3 General feeder assembly (type of coordination 1) The SIRIUS 3RW30 or 3RW40 soft starter is connected into the motor feeder between the motor starter protector and the motor. L1 3/N/PE~ 50 Hz 400 V L2 L3 PE 4 4 0 8 9 : 8 9 : : 8 9 : 8 9 Figure 8-1 Block diagram of the SIRIUS 3RW40 soft starter Note For the component design, refer to chapter Technical data (Page 127).
Installation / mounting 8.4 Soft starter with line contactor (type of coordination 1) 8.4 Soft starter with line contactor (type of coordination 1) If electrical isolation is specified, you can install a motor contactor between the soft starter and the motor starter protector.
Installation / mounting 8.5 Soft starter assembly with type of coordination 2 8.5 Soft starter assembly with type of coordination 2 The SIRIUS 3RW40 soft starter has internal protection to prevent overloading of the thyristors. The SIRIUS 3RW30 soft starter has no internal protection to prevent overloading of the thyristors. The soft starter must always be dimensioned according to the duration of the startup process and the desired starting frequency.
Installation / mounting 8.5 Soft starter assembly with type of coordination 2 Note Minimum and maximum configuration of the semiconductor fuses The fuses for the minimum and maximum configuration are specified in chapter Technical data (Page 127). Minimum configuration: The fuse is optimized for the thyristor's I²t value. If the thyristor is cold (ambient temperature) and the startup process lasts a maximum of 20 s at 3.5 times the rated current of the device, the fuse does not trip.
Installation / mounting 8.6 Capacitors to improve the power factor 8.6 Capacitors to improve the power factor CAUTION No capacitors must be connected to the output terminals of the soft starter. If so, the soft starter will be damaged. Active filters, e.g. for power factor correction, must not be operated parallel to the motor control device. If capacitors are to be used to correct the power factor, they must be connected on the device's line side.
Installation / mounting 8.
9 Connecting 9.1 Electrical connection 9.1.1 Control and auxiliary terminals The SIRIUS 3RW30 and 3RW40 soft starters can be supplied with two different connection technologies: ● Screw-type technology ● Spring-loaded technology 9.1.2 Main circuit connection SIRIUS 3RW30 and 3RW40 soft starters up to the 55 kW / 75 hp size at 400 V / 480 V are designed with removable terminals at the main circuit connections. Sizes 3RW30 1. to 3RW30 4.
Connecting 9.1 Electrical connection Sizes 3RW40 2. to 3RW40 4. 1L1, 3L2, 5L3 1 L1 3 L2 A1 1 110-230V IN A2 5 L3 13 14/24 A2, A1, 1, 13, 14/24, 23 23 OVERLOAD RESET MODE NO ON/RUN NO BYPASSED DEVICE SIRIUS OVERLOAD DEVICE RESET MODE STATE/BYPASSED STATE/BYPASSED RESET /TEST FAILURE FAILURE x Ie RESET/TEST I 5 1.3 5 10 t RESET MODE RESET MODE 20s 0 20 15 OFF 10 U 40 100% CLASS Ie 10 36 3RW40..-.BB.. 95 95, 96, 98 70 3RW40..-.TB..
Connecting 9.1 Electrical connection Sizes 3RW40 5. and 3RW40 7. Sizes 3RW40 5. and 3RW40 7. have busbar connections for the main circuit connection. Box terminals can be retrofitted on these devices as optional accessories (refer to chapter Accessories (Page 211)).
Connecting 9.
10 Operation 10.
Operation 10.2 Operator controls, displays, and connections on the 3RW40 10.
RW-01200 Operation 10.2 Operator controls, displays, and connections on the 3RW40 1 2 3RW40 2...
Operation 10.
Configuration 11.1 11 Configuration in general The SIRIUS 3RW30 and 3RW40 electronic soft starters are designed for normal starting. A larger size may need to be selected for longer ramp-up times or a higher starting frequency. An appropriately dimensioned SIRIUS 3RW40 or 3RW44 soft starter should be chosen for startup processes with motor ramp-up times > 20 s. The motor feeder between the soft starter and motor must not contain any capacitive elements (such as compensation systems).
Configuration 11.1 Configuration in general 11.1.1 Configuration procedure 1. Select the correct starter What application must be started and what functionality must be provided by the soft starter? Chapter Selecting the optimum soft starter (Page 78) 2. Take account of the startup class and the switching frequency Chapters Startup class (Page 81) and Calculating the permissible switching frequency (Page 87) 3.
Configuration 11.
Configuration 11.1 Configuration in general Note SIRIUS 3RW44 soft starter For more information about the SIRIUS soft starter, refer to the 3RW44 System Manual. You can download (http://support.automation.siemens.com/WW/llisapi.dll?func=cslib.csinfo&lang=de&objID=20 356385&subtype=133300) the manual free of charge.
Configuration 11.2 Startup class 11.2 Startup class To achieve the optimum soft starter design, it is important to know and take into account the ramp-up time (startup class) of the application. Long ramp-up times mean a higher thermal load on the thyristors of the soft starter. An appropriately dimensioned SIRIUS 3RW40 or 3RW44 soft starter should be chosen for startup processes with a motor ramp-up time > 20 s. The maximum permissible ramp-up time for SIRIUS 3RW30 soft starters is 20 seconds.
Configuration 11.2 Startup class 11.2.1 Application examples for normal starting (CLASS 10) with 3RW30 and 3RW40 Recommended basic parameter settings Assuming the conditions and constraints indicated below apply, the size of the soft starters can be equivalent to the motor rating for a normal starting characteristic (CLASS 10). You can find a suitable soft starter for the required motor rating based on the required startup class in chapter Technical data (Page 127).
Configuration 11.2 Startup class 11.2.2 Application examples for heavy-duty starting (CLASS 20): 3RW40 only Recommended basic parameter settings Assuming the conditions and constraints indicated below apply, the soft starter size must be at least one power class higher than the motor rating for heavy-duty starting (CLASS 20). You can find a suitable soft starter for the required motor rating based on the required startup class in chapter Technical data (Page 127).
Configuration 11.3 ON time and switching frequency 11.3 ON time and switching frequency Based on the rated motor current and the startup class, the SIRIUS 3RW30 and 3RW40 soft starters are dimensioned for a maximum permissible switching frequency in combination with a relative ON time (refer to chapter Technical data (Page 127)). If these values are exceeded, a larger soft starter may have to be selected.
Configuration 11.4 Reducing the rated data 11.4 Reducing the rated data You can reduce the rated data of the SIRIUS 3RW30 and 3RW40 soft starters if ● The installation altitude is higher than 1000 m. ● The ambient temperature in the switching device's environment exceeds 40 °C. ● The lateral clearances described earlier are not complied with, e.g. side-by-side assembly or direct mounting of other switching devices (assembly type). ● The vertical mounting position is not complied with. 11.
Configuration 11.5 Installation altitude and ambient temperature SIRIUS 3RW30 and 3RW40 soft starters are designed for operation with nominal current at an ambient temperature of 40 °C. If this temperature is exceeded, e.g.
Configuration 11.6 Calculating the permissible switching frequency 11.6 Calculating the permissible switching frequency 11.6.1 Table of permissible assembly combinations with switching frequency factors The factors indicated in the table refer to the switching frequency (starts / hour) as specified in chapter Technical data (Page 127). 9HUWLFDO PRXQWLQJ 5: *UDSK $VVHPEO\ W\SH 5: 5: RSWLRQDO IDQ 5: 5: 5: 5: 5: 5: 5: 5: 5: 5: $ % & ' 6WDQGDORQH DVV
Configuration 11.6 Calculating the permissible switching frequency 'LUHFW PRXQWLQJ RI 5: ZLWK 59 PRWRU VWDUWHU SURWHFWRU DQG 5$ OLQN PRGXOH 6RIW VWDUWHU DVVHPEO\ JHQHUDO 'LDJUDP $ 5 : 'LDJUDP % 5 : 5 : 'LDJUDP ' 'LDJUDP & 5 : $VVHPEO\ RI 5: ZLWK 59 PRWRU VWDUWHU SURWHF WRU ZLWK FDEOH WKH FOHDUDQFH EHWZHHQ WKH 59 DQG 5: FRUUHVSRQGV WR WKH PLQLPXP FOHDUDQFH E LQ WKH GLDJUDP RI FOHDUDQFHV IURP RWKHU GHYLFHV 'LDJUDP $ 59 59 59 59 5$ 5$ 5$ 5$ 5: 5: 5: 5:
Configuration 11.6 Calculating the permissible switching frequency $VVHPEO\ RI 5: ZLWK 59 PRWRU VWDUWHU SURWHFWRU 5$ OLQN PRGXOH FDEOH DQG 57 OLQH FRQWDFWRU 7KH PLQLPXP FOHDUDQFH EHWZHHQ WKH 5: 59 DQG 57 FRUUHVSRQGV WR WKH PLQLPXP FOHDUDQFH E F LQ WKH GLDJUDP RI FOHDUDQFHV IURP RWKHU GHYLFHV 'LDJUDP $ 'LDJUDP % 'LDJUDP $ 'LDJUDP % 5 9 5 9 5 9 5 9 5 9 5 9 5 9 5 9 5 $ 5 $ 5 $ 5 $ 5 $ 5 $ 5 $ 5 $ 5 7 5 7 5 7 5 7 5 : 5 : 5 : 5 : 5 : 5 :
Configuration 11.6 Calculating the permissible switching frequency E 11 3 5 a MLFB a (mm) a (in) b (mm) b (in) c (mm) c (in) 3RW30 1./3RW30 2. 15 0.59 60 2.36 40 1.56 3RW30 3./3RW30 4 30 1.18 60 2.36 40 1.56 3RW40 2. 15 0.59 60 2.36 40 1.56 3RW40 3./3RW40 4. 30 1.18 60 2.36 40 1.56 3RW40 5./3RW40 7. 5 0.2 100 4 75 3 a 2 4 6 F Clearances from other devices 11.6.
Configuration 11.6 Calculating the permissible switching frequency Calculating the number of starts / hour of a 3RW40 for side-by-side assembly and vertical mounting 'LDJUDP % 9HUWLFDO PRXQWLQJ *UDSK $ % 5 9 5 9 5 9 & ' $VVHPEO\ W\SH 5: 6WDQGDORQH DVVHPEO\ 6LGH E\ VLGH DVVHPEO\ 6WDQGDORQH DVVHPEO\ 6LGH E\ VLGH DVVHPEO\ 5: 5: 5: 5: 5: 5: 5: 5: RSWLRQDO IDQ 5: 5: 5: 5:
Configuration 11.7 Configuration aids 11.7 Configuration aids 11.7.1 Online configurator Using the online configurator, you can select soft starters based on the rated motor data and the specified device functionality. The selection of the soft starter is subject to fixed conditions and constraints, such as switching frequency, startup class etc. These conditions cannot be changed. You can find the online configurator at www.siemens.de/sanftstarter (https://mall.automation.siemens.
Configuration 11.7 Configuration aids 11.7.4 SIRIUS soft starter training course (SD-SIRIUSO) SIEMENS offers a two-day training course on SIRIUS electronic soft starters to keep both customers and our own employees up to date with the latest information about configuring, commissioning, and maintenance. Please address all inquiries and enrollments to: Training Center Erlangen A&D PT 4 Werner-von-Siemens-Str. 65 D-91052 Erlangen Phone: ++49 9131 729262 Fax: ++49 9131 728172 e-mail: (mailto:sibrain.
Configuration 11.8 Order number system for the 3RW30 11.8 Order number system for the 3RW30 5 : % % 6SHFLDO YHUVLRQV 5DWHG RSHUDWLRQDO YROWDJH 8H 5DWHG FRQWURO VXSSO\ YROWDJH 8V 6RIW VWDUWHU IXQFWLRQDOLW\ %% %\SDVV HWF &RQQHFWLRQ W\SH VFUHZ VSULQJ ORDGHG WHUPLQDO 6L]H UDWHG RSHUDWLQJ FXUUHQW ,H 6RIW VWDUWHU W\SH 6RIW VWDUWHU Rated current and rated power at Ue= 400 V / 460 V and Tamb = 40 °C / 50 °C 13 Ie = 3.6 A / 3 A Pe = 1.5 kW / 1.5 hp 14 Ie = 6.5 A / 4.
Configuration 11.9 Order number system for the 3RW40 11.9 Order number system for the 3RW40 5 : % % 6SHFLDO YHUVLRQV 5DWHG RSHUDWLRQDO YROWDJH 8H 5DWHG FRQWURO VXSSO\ YROWDJH 8V 6RIW VWDUWHU IXQFWLRQDOLW\ %% E\SDVV 7% E\SDVV WKHUPLVWRU HWF &RQQHFWLRQ W\SH VFUHZ VSULQJ ORDGHG 6L]H UDWHG RSHUDWLRQDO FXUUHQW ,H 6RIW VWDUWHU W\SH 6RIW VWDUWHU Rated current and rated power at Ue= 400 V / 460 V and Tamb = 40 °C / 50 °C 24 Ie = 12.5 A / 11 A Pe = 5.5 kW / 7.
Configuration 11.
Commissioning 12.1 12 Before commencing work: Isolating the equipment from the supply system and ensuring that it cannot be reconnected. DANGER Hazardous voltage Will cause death or serious injury. • Disconnect the system and all devices from the power supply before starting work. • Secure against switching on again. • Verify that the equipment is not live. • Ground and short-circuit. • Erect barriers around or cover adjacent live parts. DANGER Hazardous voltage Will cause death or serious injury.
Commissioning 12.2 Commissioning the 3RW30 12.2 Commissioning the 3RW30 Commissioning, description of the start and output parameters 12.2.1 Commissioning procedure 1. Check the voltages and wiring. 2. Set the start parameters (for recommended parameters, refer to the quick commissioning table). 3. Start up the motor and if necessary optimize the parameters (refer to the quick commissioning table). 4. Document the parameter settings if required (refer to chapter Table of parameters used (Page 219)).
Commissioning 12.2 Commissioning the 3RW30 12.2.2 Quick commissioning of the 3RW30 and optimization of the parameters 4XLFN FRPPLVVLRQLQJ RI 6,5,86 5: VRIW VWDUWHU &$87,21 5LVN RI SURSHUW\ GDPDJH &RQQHFWLRQ WR XQDVVLJQHG WHUPLQDOV LV QRW SHUPLWWHG &KHFN WKH ZLULQJ &RQWURO XQLW DQG 3RZHU XQLW 6WDUW SDUDPHWHUV 5HFRPPHQGHG VHWWLQJ 6WDUWLQJ YROWDJH 3DUDPHWHUL]H WKH GHYLFH 6RIW VWDUW IXQFWLRQ 5DPS WLPH V 6WDUWLQJ YROWDJH 6HW WR WKH UHTXLUHG YDOXHV UHIHU WR WDEOH RI UHFRPPHQG
Commissioning 12.2 Commissioning the 3RW30 12.2.3 Setting the soft start function Voltage ramp The SIRIUS 3RW30 achieves soft starting by means of a voltage ramp. The motor terminal voltage is increased from a parameterizable starting voltage to the mains voltage within a definable ramp time.
Commissioning 12.2 Commissioning the 3RW30 12.2.4 Setting the starting voltage U potentiometer The starting voltage value is set with the U potentiometer. This value determines the starting torque of the motor. A lower starting voltage results in a lower starting torque (softer start) and a lower starting current. The starting voltage selected must be sufficiently high to ensure that motor starts up smoothly as soon as the start command is received by the soft starter. 12.2.
Commissioning 12.2 Commissioning the 3RW30 The SIRIUS 3RW30 soft starter can be damaged in this application (set ramp time shorter than the actual motor ramp-up time). A maximum ramp-up time of 20 s is possible for the 3RW30. An appropriately dimensioned SIRIUS 3RW40 or 3RW44 soft starter should be chosen for startup processes with a motor ramp-up time > 20 s. CAUTION Risk of property damage Make sure the selected ramp time is longer than the actual motor ramp-up time.
Commissioning 12.3 3RW30: LEDs and troubleshooting 12.3 3RW30: LEDs and troubleshooting /('V RQ 5: 6RIW VWDUWHU '(9,&( UG JQ \OZ 5: $X[LOLDU\ FRQWDFW 67$7( %<3$66(' )$,/85( JQ UG 21 8V 2SHUDWLQJ VWDWH ,1 2II JQ 6WDUW JQ %\SDVVHG JQ JQ JQ )DXOW ,PSHUPLVVLEOH HOHFWURQLFV VXSSO\ YROWDJH %\SDVV RYHUORDG UG 0LVVLQJ ORDG YROWDJH 3KDVH IDLOXUH PLVVLQJ ORDG 'HYLFH IDXOW \OZ UG JQ UG UG UG /('V 2II 21 )ODVKLQJ JQ UG \OZ *UHHQ 5HG
Commissioning 12.3 3RW30: LEDs and troubleshooting For notes on troubleshooting, refer to the table below. Fault Cause Remedy Impermissible electronics supply voltage The control supply voltage does not correspond to the soft starter's rated voltage. Check the control supply voltage; an incorrect control supply voltage could be caused by a power failure or a voltage dip. Bypass overload A current > 3.5 x Ie of the soft starter occurs for > 60 ms in bypass mode (e.g. because the motor is blocked).
Commissioning 12.4 Commissioning the 3RW40 12.4 Commissioning the 3RW40 Commissioning, description of the start, stop, motor protection, and output parameters 12.4.1 Commissioning procedure 1. Check the voltages and wiring. 2. Set the start and stop parameters (for recommended parameters, refer to the quick commissioning table). 3. Set the motor overload function (if required) 4. Define the RESET mode if a failure occurs. 5.
Commissioning 12.4 Commissioning the 3RW40 12.4.2 Quick commissioning of the 3RW40 and optimization of the parameters 4XLFN FRPPLVVLRQLQJ RI 6,5,86 5: VRIW VWDUWHU &$87,21 5LVN RI SURSHUW\ GDPDJH &RQQHFWLRQ WR XQDVVLJQHG WHUPLQDOV LV QRW SHUPLWWHG 5HFRPPHQGHG VHWWLQJ $SSOLFDWLRQ 6WDUW SDUDPHWHUV 6WDUWLQJ 5DPS WLPH &XUUHQW OLPLWLQJ YROWDJH V YDOXH V 6WRS SDUDPHWHU 5DPS GRZQ WLPH V [ ,H V &RQYH\RU EHOW [ ,H 5ROOHU FRQYH\RU [
Commissioning 12.4 Commissioning the 3RW40 12.4.3 Setting the soft start function Voltage ramp The SIRIUS 3RW40 achieves soft starting by means of a voltage ramp. The motor terminal voltage is increased from a parameterizable starting voltage to the mains voltage within a definable ramp time.
Commissioning 12.4 Commissioning the 3RW40 12.4.4 Setting the starting voltage U potentiometer The starting voltage value is set with the U potentiometer. This value determines the starting torque of the motor. A lower starting voltage results in a lower starting torque (softer start) and a lower starting current. The starting voltage selected must be sufficiently high to ensure that motor starts up smoothly as soon as the start command is received by the soft starter. 12.4.
Commissioning 12.4 Commissioning the 3RW40 12.4.6 Current limiting in conjunction with a starting voltage ramp and ramp-up detection Current limiting 0RWRU FXUUHQW , ,GLUHFW PRWRU VWDUWLQJ , 6RIW VWDUWHU 6HWWDEOH FXUUHQW OLPLWLQJ YDOXH 6WDUW GHWHUPLQHG E\ VHW VWDUW PRGH LQ WKLV FDVH YROWDJH UDPS ,H PRWRU QH PRWRU 0RWRU VSHHG Q The SIRIUS 3RW40 soft starter measures the phase current (motor current) continuously with the help of integrated current transformers.
Commissioning 12.4 Commissioning the 3RW40 The rated operational current of the motor must be set with the Ie potentiometer according to the mains voltage and the motor connection (wye-delta). The electronic motor overload protection also refers to this set value if it is active. For the permissible settings referred to the required motor overload trip class, refer to chapter Motor current settings (Page 113). 12.4.
Commissioning 12.5 Setting the soft stop function 12.5 Setting the soft stop function In "soft stop" mode, the natural stop process of the load is decelerated. The function is used when the load must be prevented from stopping abruptly. This is typically the case in applications with a low mass inertia or a high counter-torque. 9ROWDJH 8 LQ 8PDLQV 5DPS GRZQ WLPH 7LPH W V 6WRS FRPPDQG RQ VRIW VWDUWHU 12.5.
Commissioning 12.6 Setting the motor protection function 12.6 Setting the motor protection function The motor overload protection function is implemented on the basis of the winding temperature. This indicates whether the motor is overloaded or functioning in the normal operating range. The winding temperature can either be calculated with the help of the integrated, electronic motor overload function or measured with a connected motor thermistor. 12.6.
Commissioning 12.6 Setting the motor protection function You can set different CLASS characteristics according to the startup class. If the potentiometer is set to OFF, the "electronic motor overload protection" function is deactivated. Note The rated data of the soft starters refers to normal starting (CLASS 10). The starters may need to be calculated with a size allowance for heavy-duty starting (> CLASS 10).
Commissioning 12.7 Thermistor motor protection 12.7 Thermistor motor protection (Optional for 3RW40 2. to 3RW40 4. with 24 V AC/DC rated control voltage) .OL[RQ WKHUPLVWRU 7\SH $ 37& WKHUPLVWRU Thermistor motor protection After removing the copper jumper between T11/21 and T22, you can connect and evaluate either a Klixon thermistor integrated in the motor winding (at terminal T11/T21-T22) or a type A PTC (at terminal T11/T21-T12). 12.
Commissioning 12.9 Functions of the outputs 12.9 Functions of the outputs 12.9.1 Functions of the BYPASSED and ON / RUN outputs IN 13/14 tR on UN tR off t tR off t tR off t U US tR on ON 13/14 RUN 13/14 BYPASSED 23/24 tR on BYPASSED output contact The BYPASSED output at terminal 23 / 24 closes as soon as the SIRIUS 3RW40 soft starter detects that the motor has started up (refer to chapter Ramp-up detection (Page 110)).
Commissioning 12.9 Functions of the outputs If the RUN function is set, you can control a line contactor during the startup process, operation, or the set soft stop (refer to chapter Control with an optional main / line contactor (Page 188)) For recommended circuits, refer to chapter Typical circuit diagrams (Page 175). 12.9.
Commissioning 12.9 Functions of the outputs ( ' & % $ 3UHVV WR VWRUH 5(6(7 7(67 ! V ! V +ROG SUHVVHG GRZQ 5(6(7 02'( ! V JQ '(9,&( JQ 67$7( %<3$66(' 2)) 2)) )$,/85( 2)) 2)) $872 2)) 21 UG UG 21 581 581 21 2)) )ODVKLQJ 3UHVV EULHIO\ WR FKDQJH ! V 2)) JQ 2)) 2)) )OLFNHULQJ Reparameterizing the ON / RUN output A: Control voltage is present and the soft starter is in the normal, fault-free position: The DEVICE LED is continuously l
Commissioning 12.9 Functions of the outputs E: Exit programming and save the settings: Press the RESET / TEST MODE button (1) for longer than 1 s until the DEVICE LED (3) lights up (green). The LEDs indicate the following states again if the output was successfully parameterized: DEVICE LED: Continuously lit (green). STATE / BYPASSED and FAILURE LEDs: Off. The AUTO LED indicates the color of the set RESET mode. 12.9.
Commissioning 12.10 RESET MODE and functions of the RESET / TEST button 12.10 RESET MODE and functions of the RESET / TEST button 12.10.1 SIRIUS 3RW40 2. to 3RW40 4. soft starters 12.10.1.1 Setting the RESET MODE Position of the RESET button behind the label on the 3RW40 2. 1 2 3RW40 2... 3 RESET MODE AUTO RESET Yellow Manual RESET Off Remote RESET Green RESET MODE button By pressing the RESET MODE button, you define the reset procedure in case of a fault.
Commissioning 12.10 RESET MODE and functions of the RESET / TEST button 12.10.1.3 Remote RESET 1 / / / 5(6(7 21 2)) 8V $ $ ! V W Remote RESET (RESET MODE LED = green) You can reset a fault signal by disconnecting the control supply voltage for >1.5 s. 12.10.1.4 AUTO RESET AUTO RESET (RESET MODE LED = yellow) If you set the RESET mode to AUTO, a fault is automatically reset.
Commissioning 12.10 RESET MODE and functions of the RESET / TEST button 12.10.2 SIRIUS 3RW40 5. to 3RW40 7. soft starters 12.10.2.1 Setting the RESET MODE AUTO RESET Yellow Manual / (remote) RESET Off RESET MODE button By pressing the RESET MODE button, you define the reset procedure in case of a fault. This is indicated by the AUTO LED. 12.10.2.2 Manual RESET RESET / TEST button (AUTO LED off) You can reset a fault by pressing the RESET / TEST button. 12.10.2.
Commissioning 12.10 RESET MODE and functions of the RESET / TEST button Remote RESET with module for RESET (AUTO LED = off) You can perform a remote RESET (the RESET MODE set on the starter is MANUAL RESET) by controlling the optional module for RESET (3RU1900-2A). 12.10.2.4 AUTO RESET AUTO RESET (AUTO LED = yellow) If you set the RESET mode to AUTO, a fault is automatically reset.
Commissioning 12.11 3RW40: LEDs and troubleshooting 12.11 3RW40: LEDs and troubleshooting /(' VWDWXVHV 5: $X[LOLDU\ FRQWDFWV 0RWRU SURWHFWLRQ 6RIW VWDUWHU 67$7( 5(6(7 02'( %<3$66(' 29(5/2$' $872 '(9,&( )$,/85( UG \OZ JQ UG JQ \OZ JQ UG 5: 21 581 )$,/85( %<3$66(' 29(5/2$' 8V 2SHUDWLQJ VWDWH ,1 2II JQ 6WDUW JQ JQ %\SDVVHG JQ JQ 6WRS JQ JQ :DUQLQJ ,H FODVV VHWWLQJ LPSHUPLVVLEOH JQ 6WDUW LQKLELWHG GHYLFH WRR ZDUP FRR
Commissioning 12.11 3RW40: LEDs and troubleshooting WARNING Automatic restart Can result in death, serious injury, or property damage. The automatic RESET mode (AUTO RESET) must not be used in applications where there is a risk of serious injury to persons or substantial damage to property if the motor starts up again unexpectedly. The start command (e.g.
Commissioning 12.11 3RW40: LEDs and troubleshooting Fault Cause Remedy Impermissible electronics supply voltage: The control supply voltage does not correspond to the soft starter's rated voltage. Check the control supply voltage; could be caused by a power failure, voltage dip, or incorrect control supply voltage. Use a stabilized power supply unit if due to mains fluctuations.
Commissioning 12.11 3RW40: LEDs and troubleshooting Fault Device fault 126 Cause Remedy Cause 3: Motor phase T1 / T2 / T3 is not connected. Connect the motor properly (e.g. jumpers in the motor terminal box, repair switch closed etc.) Soft starter defective. Contact your SIEMENS partner or Technical Assistance.
Technical data 13.1 3RW30 13.1.1 Overview 13 SIRIUS 3RW30 soft starters reduce the motor voltage through variable phase angle control and increase it from a selectable starting voltage up to the mains voltage within the ramp time. They limit the starting current and torque, so that the shocks that occur during direct starts or wye-delta starting are avoided. Mechanical loads and mains voltage dips can be effectively prevented in this way.
Technical data 13.1 3RW30 13.1.
Technical data 13.1 3RW30 Note The rated motor current is extremely important when selecting a soft starter. Refer to the information about selecting soft starters in chapter Configuration (Page 77). Conditions for normal starting: Max. ramp time 3 s, starting current 300 %, 20 starts / hour, ON time 30 %, standalone assembly, max. installation altitude 1000 m / 3280 ft, ambient temperature kW 40 °C / 104 °F.
Technical data 13.1 3RW30 13.1.3 3RW30..-.BB.. control electronics 7\SH 5: 5: 5: 5: 9 s s P$ P$ P$ +] s &RQWURO HOHFWURQLFV 7HUPLQDO $ $ 5DWHG YDOXHV 5DWHG FRQWURO VXSSO\ YROWDJH ವ 7ROHUDQFH 5DWHG FRQWURO VXSSO\ FXUUHQW ವ 67$1'%< ವ 'XULQJ SLFNXS ವ 21 5DWHG IUHTXHQF\ ವ 7ROHUDQFH &RQWURO LQSXW ,1 3RZHU FRQVXPSWLRQ ZLWK YHUVLRQ ವ 9 '& ವ 9 $& 5HOD\ RX
Technical data 13.1 3RW30 13.1.5 3RW30..-.BB.. power electronics 7\SH 5: %% 5: %% 3RZHU HOHFWURQLFV 5DWHG RSHUDWLRQDO YROWDJH 7ROHUDQFH 5DWHG IUHTXHQF\ 7ROHUDQFH 9 $& +] s &RQWLQXRXV GXW\ DW r& RI ,H 0LQLPXP ORDG RI ,H DW OHDVW $ 0D[LPXP FDEOH OHQJWK EHWZHHQ VRIW VWDUWHU DQG PRWRU P 3HUPLVVLEOH LQVWDOODWLRQ DOWLWXGH P 'HUDWLQJ IURP VHH FKDUDFWHULVWLF FXUYHV KLJKHU RQ UHTXHVW 3HUPLVVLEOH DPELHQW WHPS
Technical data 13.1 3RW30 13.1.7 3RW30 26, 27, 28-.BB.. power electronics 7\SH 5: 5: 5: $ $ $ ವ'XULQJ RSHUDWLRQ DIWHU VWDUWXS RI WKH PRWRU DW XQLQWHUUXSWHG UDWHG RSHUDW FXUU r& DSSUR[ : ವ'XULQJ VWDUWLQJ DW ,0 r& : $ K $ K 3RZHU HOHFWURQLFV &XUUHQW FDUU\LQJ FDSDFLW\ UDWHG RSHUDWLQJ FXUUHQW ,H ವ$FF W
Technical data 13.1 3RW30 13.1.9 3RW30 main conductor cross-sections 6RIW VWDUWHU 7\SH 5: 5: 5: 5: &RQGXFWRU FURVV VHFWLRQV 6FUHZ WHUPLQDOV 0DLQ FRQGXFWRUV )URQW FODPSLQJ SRLQW FRQQHFWHG ವ 6ROLG PP [ [ [ [ [ DFF WR ,(& DFF WR ,(& PD[ [ [ ವ )LQHO\ VWUDQGHG ZLWK HQG VOHHYH PP [ [ [ [ [ [
Technical data 13.1 3RW30 13.1.10 6RIW VWDUWHUV 3RW30 auxiliary conductor cross-sections 7\SH 5: 5: &RQGXFWRU FURVV VHFWLRQV $X[LOLDU\ FRQGXFWRUV RU FRQGXFWRUV FDQ EH FRQQHFWHG 6FUHZ WHUPLQDOV ವ 6ROLG ವ )LQHO\ VWUDQGHG ZLWK HQG VOHHYH PP PP [ [ ವ $:* FDEOHV 6ROLG RU VWUDQGHG )LQHO\ VWUDQGHG ZLWK HQG VOHHYH $:* $:* [ [ 1P OE LQ PP PP $:* [ [ [ ವ 7HUPLQDO VFUHZ
Technical data 13.1 3RW30 13.1.12 6RIW VWDUWHU W\SHV Recommended filters 1RPLQDO FXUUHQW 5HFRPPHQGHG ILOWHUV 6RIW VWDUWHU 9ROWDJH UDQJH WR 9 )LOWHU W\SHV 1RPLQDO FXUUHQW ILOWHUV $ $ 7HUPLQDOV PP 5: b 5: b 5: b () $$ () $$ () $$ 5: b 5: b () $$ () $$ 7KH UDGLR LQWHUIHUHQFH VXSSUHVVLRQ ILOWHU LV XVHG WR UHPRYH WKH FRQGXFWHG LQWHUIHUHQFH IURP WKH PDLQ FLUFXLW 7KH ILHOG
Technical data 13.1 3RW30 13.1.14 Fuseless version )XVHOHVV YHUVLRQ 4 0 a &LUFXLW EUHDNHU 6RIW VWDUWHU 7R& 5DWHG FXUUHQW 5DWHG FXUUHQW 9 4 7\SH 16% B 4 $ 4 ,T PD[ 7\SH N$ $ 7\SH RI FRRUGLQDWLRQ 5: 59 ($ 5: 5: 59 )$ 59 +$ 59 ($ SUHOLP 59 )$ 59 +$ 5: 5: 5: 59 -$ 59 .$ 59 %$ 59 -$ 59 .
Technical data 13.1 3RW30 13.1.15 Fused version (line protection only) )XVHG YHUVLRQ OLQH SURWHFWLRQ RQO\ ) 4 0 a 6RIW VWDUWHUV 1RPLQDO 7R& FXUUHQW 16% B 4 /LQH SURWHFWLRQ PD[LPXP 5DWHG FXUUHQW /LQH FRQWDFWRUV 6L]H 4 ) 7\SH $ 7\SH $ 7\SH RI FRRUGLQDWLRQ ,T N$ DW 9 RSWLRQDO 4 5: 1$ 57 57 5: b 5: b 1$ 1$ 57 57 57 57 5: b 5: b 5: b
Technical data 13.1 3RW30 13.1.16 Fused version with SITOR 3NE1 fuses Assembly as for type of coordination 2, with SITOR all-range fuses (F´1) for combined thyristor and line protection.
Technical data 13.1 3RW30 13.1.17 Fused version with SITOR 3NE3/4/8 fuses Assembly as for type of coordination 2, with additional SITOR fuses (F3) for thyristor protection only. )XVHG YHUVLRQ ZLWK 1( 6,725 IXVHV VHPLFRQGXFWRU SURWHFWLRQ E\ IXVH OLQH DQG RYHUORDG SURWHFWLRQ E\ PRWRU VWDUWHU SURWHFWRU DOWHUQDWLYHO\ LQVWDOODWLRQ ZLWK FRQWDFWRU DQG RYHUORDG UHOD\ SRVVLEOH )RU VXLWDEOH IXVH EDVHV UHIHU WR 6(17521 VZLWFKLQJ DQG SURWHFWLQJ GHYLFHV IRU SRZHU GLVWULEXWLRQ ದದ! 6ZLWFK GLVFRQQHFWRUV WK
Technical data 13.1 3RW30 6RIW VWDUWHUV 1RPLQDO 7R& FXUUHQW /LQH FRQWDFWRUV RSWLRQDO 0RWRU VWDUWHU SURWHFWRUV 9 5DWHG FXUUHQW 4 7\SH 4 4 7\SH $ $ /LQH SURWHFWLRQ PD[LPXP 5DWHG FXUUHQW 6L]H ) 7\SH 7\SH RI FRRUGLQDWLRQ ,T N$ DW 9 $ 5: 57 57 59 ($ 59 ($ SURYLV 1$ 5: b 5: b 57 57 57 57 1$ 1$ 57 57 5
Technical data 13.2 3RW40 13.2 3RW40 13.2.1 Overview SIRIUS 3RW40 soft starters have all the same advantages as the 3RW30 soft starters. SIRIUS 3RW40 soft starters are characterized above all by their small space requirements. Integral bypass contacts mean that no power loss has to be taken into account at the power semiconductors (thyristors) after the motor has started up. This cuts down on heat losses, enabling a more compact design and making external bypass circuits superfluous.
Technical data 13.2 3RW40 13.2.
Technical data 13.2 3RW40 Note The rated motor current is extremely important when selecting a soft starter. Refer to the information about selecting soft starters in chapter Configuration (Page 77). Conditions for normal starting (CLASS 10): Max. ramp-up time 10 s, current limiting 300 %, 5 starts / hour, ON time 30 %, standalone assembly, max. installation altitude 1000 m / 3280 ft, ambient temperature kW 40 °C / 104 °F.
Technical data 13.2 3RW40 13.2.
Technical data 13.2 3RW40 Note The rated motor current is extremely important when selecting a soft starter. Refer to the information about selecting soft starters in chapter Configuration (Page 77). Conditions for normal starting (CLASS 10): Max. ramp-up time 10 s, current limiting 300 %, 5 starts / hour, ON time 30 %, standalone assembly, max. installation altitude 1000 m / 3280 ft, ambient temperature kW 40 °C / 104 °F.
Technical data 13.2 3RW40 13.2.
Technical data 13.2 3RW40 Note The rated motor current is extremely important when selecting a soft starter. Refer to the information about selecting soft starters in chapter Configuration (Page 77). Conditions for normal starting (CLASS 10): Max. ramp-up time 10 s, current limiting 300 %, 5 starts / hour, ON time 30 %, standalone assembly, max. installation altitude 1000 m / 3280 ft, ambient temperature kW 40°C / 104 °F.
Technical data 13.2 3RW40 13.2.
Technical data 13.2 3RW40 Note The rated motor current is extremely important when selecting a soft starter. Refer to the information about selecting soft starters in chapter Configuration (Page 77). Conditions for normal starting (CLASS 10): Max. ramp-up time 20 s, current limiting 300 %, 5 starts / hour, ON time 30 %, standalone assembly, max. installation altitude 1000 m / 3280 ft, ambient temperature kW 40 °C / 104°.
Technical data 13.2 3RW40 13.2.
Technical data 13.2 3RW40 Note The rated motor current is extremely important when selecting a soft starter. Refer to the information about selecting soft starters in chapter Configuration (Page 77). Conditions for normal starting (CLASS 10): Max. ramp-up time 40 s, current limiting 350 %, 1 starts / hour, ON time 30 %, standalone assembly, max. installation altitude 1000 m / 3280 ft, ambient temperature kW 40 °C / 104 °F.
Technical data 13.2 3RW40 13.2.7 3RW40 2., 3., 4. control electronics 5: 7\SH 5: 5: &RQWURO HOHFWURQLFV 7HUPLQDO $ $ 9 5DWHG YDOXHV 5DWHG FRQWURO VXSSO\ YROWDJH ವ 7ROHUDQFH s s $SSUR[ $SSUR[ 5DWHG FRQWURO VXSSO\ FXUUHQW ವ 67$1'%< ವ 'XULQJ SLFNXS ವ 21 ZLWKRXW IDQ ವ 21 ZLWK IDQ P$ P$ P$ P$ 5DWHG IUHTXHQF\ ವ 7ROHUDQFH
Technical data 13.2 3RW40 13.2.9 3RW40 2., 3., 4. control electronics 5: 5: 5: 7\SH &RQWURO HOHFWURQLFV /(' 2SHUDWLQJ LQGLFDWLRQV 2II 6WDUW %\SDVV 6WRS '(9,&( *UHHQ *UHHQ *UHHQ *UHHQ 67$7( %<3$66(' )$,/85( 2II *UHHQ IODVKLQJ *UHHQ *UHHQ IODVKLQJ 29(5/2$' 2II 2II 2II 2II *UHHQ
Technical data 13.2 3RW40 13.2.11 3RW40 protection functions 7\SH 5: )DFWRU\ GHIDXOW 3URWHFWLRQ IXQFWLRQV 0RWRU SURWHFWLRQ IXQFWLRQV 7ULSV LQ WKH HYHQW RI 7ULS FODVV WR ,(& &ODVV 3KDVH IDLOXUH VHQVLWLYLW\ 2YHUORDG ZDUQLQJ 7KHUPLVWRU SURWHFWLRQ DFFRUGLQJ WR ,(& W\SH $ ,(& 5HVHW RSWLRQ DIWHU WULSSLQJ 5HFRYHU\ WLPH PLQ 'HYLFH SURWHFWLRQ IXQFWLRQV 7ULSV LQ WKH HYHQW RI 7KHUPDO RYHUORDGLQJ RI WKH PRWRU ! 1R
Technical data 13.2 3RW40 13.2.13 3RW40 2. to 7. power electronics 7\SH 5: % 5: % 5: % 5: % 5: % 5: % 5: %% 5: %% 5: %% 5: %% 3RZHU HOHFWURQLFV 5DWHG RSHUDWLRQDO YROWDJH 7ROHUDQFH 9 $& 0D[LPXP WK\ULVWRU EORFNLQJ YROWDJH 9 $& 5DWHG IUHTXHQF\ 7ROHUDQFH +] s &RQWLQXRXV GXW\ DW r& RI ,H
Technical data 13.2 3RW40 13.2.14 3RW40 24, 26, 27, 28 power electronics 5: 5: 5: 5: $ $ $ $ : : $ K 5DWHG PRWRU FXUUHQW ,0 UXQ XS WLPH V 6WDUWV SHU KRXU $ K ವ )RU KHDY\ GXW\ VWDUWLQJ FODVV 5DWHG PRWRU FXUUHQW ,0 UXQ XS
Technical data 13.2 3RW40 13.2.
Technical data 13.2 3RW40 13.2.
Technical data 13.2 3RW40 13.2.17 3RW40 2., 3., 4. main conductor cross-sections 6RIW VWDUWHUV 7\SH 5: 5: 5: &RQGXFWRU FURVV VHFWLRQV 6FUHZ WHUPLQDOV 0DLQ FRQGXFWRUV )URQW FODPSLQJ SRLQW FRQQHFWHG ವ 6ROLG PP [ [ DFFRUGLQJ WR ,(& PD[ [ [ [ ವ :LWK HQG VOHHYH PP [ [ [ [ ವ 6WUDQGHG PP ದ [ [ 6ROLG $:* [ 6ROLG R
Technical data 13.2 3RW40 13.2.18 3RW40 5., 7. main conductor cross-sections 6RIW VWDUWHUV 7\SH 5: 5: &RQGXFWRU FURVV VHFWLRQV 6FUHZ WHUPLQDOV 0DLQ FRQGXFWRUV 57 * N: 57 * ವ )LQHO\ VWUDQGHG ZLWK HQG VOHHYH PP ವ 6WUDQGHG PP 0LQ [ [ 0D[ [ [ NFPLO :LWK ER[ WHUPLQDO )URQW FODPSLQJ SRLQW FRQQHFWHG ವ 5LEERQ FDEOH FRQGXFWRUV QXPEHU [ ZLGWK [ WKLFNQHVV PP 5HDU FODPSLQJ SRLQW FRQQHFWHG ವ $:* FDEOH
Technical data 13.2 3RW40 13.2.19 3RW40 .. auxiliary conductor cross-sections 6RIW VWDUWHUV 5: 7\SH &RQGXFWRU FURVV VHFWLRQV $X[LOLDU\ FRQGXFWRUV RU FRQGXFWRUV FDQ EH FRQQHFWHG 6FUHZ WHUPLQDOV ವ 6ROLG ವ )LQHO\ VWUDQGHG ZLWK HQG VOHHYH PP PP [ [ ವ $:* FDEOHV 6ROLG RU VWUDQGHG )LQHO\ VWUDQGHG ZLWK HQG VOHHYH $:* $:* [ [ 1P OE LQ 6SULQJ ORDGHG WHUPLQDOV ವ 6ROLG 5: b WR 5: b 5: 5: PP PP
Technical data 13.2 3RW40 13.2.21 6RIW VWDUWHU W\SHV Recommended filters 1RPLQDO FXUUHQW 5HFRPPHQGHG ILOWHUV 6RIW VWDUWHUV 9ROWDJH UDQJH WR 9 )LOWHU W\SHV $ 5: b 5: b 5: b 5: b 5: b () $$ () $$ () $$ () $$ () $$ 1RPLQDO FXUUHQW ILOWHUV $ 7HUPLQDOV PP 7KH UDGLR LQWHUIHUHQFH VXSSUHVVLRQ ILOWHU LV XVHG WR UHPRYH WKH FRQGXFWHG LQWHUIHUHQFH IURP WKH PDLQ FLUFXLW 7KH ILHOG UHODWH
Technical data 13.2 3RW40 13.2.23 Fuseless version )XVHOHVV YHUVLRQ 4 0 a 16% B 4 6RIW VWDUWHUV 1RPL 0RWRU VWDUWHU SURWHFWRUV 7R& 9 QDO FXUUHQW 4 4 7\SH $ 7\SH 7\SH RI FRRUGLQDWLRQ 9 5DWHG FXUUHQW 9 4 ,T PD[ N$ $ 7\SH N$ $ 59 .& 59 $& 59 $& LQ VL]H 6 59 '& 59 '& 59 (& 59 (& 59 )& 59 )& ದ ದ ದ ದ ದ ದ ದ ದ ದ ದ ದ ದ 4 ,T PD[ 7\SH 5DWHG
Technical data 13.2 3RW40 13.2.24 Fused version (line protection only) )XVHG YHUVLRQ OLQH SURWHFWLRQ RQO\ ) 4 0 a 6RIW VWDUWHUV 7R& 16% B 4 /LQH SURWHFWLRQ PD[LPXP 1RPLQDO FXUUHQW /LQH FRQWDFWRUV 5DWHG FXUUHQW 6L]H 4 ) 7\SH $ 7\SH $ 7\SH RI FRRUGLQDWLRQ ,T N$ DW 9 RSWLRQDO 4 5: b 5: b 5: b 5: b 1$ 1$ 1$ 1$ 57 57 57 57 5: b 5: b
Technical data 13.2 3RW40 13.2.25 Fused version with SITOR 3NE1 fuses Assembly as for type of coordination 2, with SITOR all-range fuses (F´1) for combined thyristor and line protection.
Technical data 13.2 3RW40 13.2.26 Fused version with SITOR 3NE3/4/8 fuses Assembly as for type of coordination 2, with additional SITOR fuses (F3) for thyristor protection only. )XVHG YHUVLRQ ZLWK 1( 6,725 IXVHV VHPLFRQGXFWRU SURWHFWLRQ E\ IXVH OLQH DQG RYHUORDG SURWHFWLRQ E\ PRWRU VWDUWHU SURWHFWRU DOWHUQDWLYHO\ LQVWDOODWLRQ ZLWK FRQWDFWRU DQG RYHUORDG UHOD\ SRVVLEOH )RU VXLWDEOH IXVH EDVHV UHIHU WR XQGHU 6(17521 VZLWFKLQJ DQG SURWHFWLQJ GHYLFHV IRU SRZHU GLVWULEXWLRQ ದದ! 6ZLWFK GLVFRQQHFWR
Technical data 13.2 3RW40 6RIW VWDUWHUV 1RPL /LQH FRQWDFWRUV 7R& QDO RSWLRQDO FXUUHQW 4 4 7\SH $ 7\SH RI FRRUGLQDWLRQ ,T N$ DW 9 57 5: b 57 57 LQ VL]H 6 57 57 5: b 57 57 5: b 57 57 5: b $ 4 7\SH $ /LQH SURWHFWLRQ PD[LPXP 5DWHG FXUUHQW ) 7\SH $ ದ ದ 1$ ದ ದ ದ ದ ದ ದ 1$ 1$ 1$ 0RWRU VWDUWHU SURWHFWRUV 5DWHG FXUUH
Technical data 13.2 3RW40 13.2.27 Motor protection tripping characteristics for 3RW40 (with symmetry) 16% B D 7ULSSLQJ WLPH W >V@ &ODVV 13.2.
Technical data 13.3 Win-Soft Starter selection and simulation software 13.3 Win-Soft Starter selection and simulation software This software can be used to simulate and select all SIEMENS soft starters, taking into account various parameters such as the supply system conditions, motor data, load data, specific application requirements, etc.
Technical data 13.
14 Dimension drawings 14.1 3RW30 for standard applications E G H K I F D P O J 16% B N L 7\SH GLPHQVLRQV PP D G H I J K 5: 5: E 5: 5: 5: 5: 'LVWDQFHV IURP J
Dimension drawings 14.2 3RW40 for standard applications 14.2 3RW40 for standard applications E G H K I P F D O J 16% B D N L 7\SH GLPHQVLRQ PP D E G H I J K L N O P 5: 5: 5: 5: 6LGH 7RS %RWWRP 5HWDLQLQJ VFUHZV 7LJKWHQLQJ WRUTXH 1P 'LVWD
Dimension drawings 14.2 3RW40 for standard applications E F G H I J K L N O P Q R S T 5: 7\SH GLPHQVLRQV PP D 0 1P 5: 0 1P SIRIUS 3RW30 / 3RW40 Manual, 10/2010, 535199502000 DS 03 173
Dimension drawings 14.
15 Typical circuit diagrams 15.1 Typical circuit for the optional thermistor motor protection evaluation A thermistor motor protection evaluation function is optionally available for the 24 V AC/DC control voltage version of the 3RW40 2 to 3RW40 4. Note If a thermistor is connected (PTC type A or Klixon), you must remove the copper jumper between terminals T11/21 and T22. 7\SH $ 37& 7KHUPRFOLFN 7 7 4 7 Figure 15-1 7 7 7 4 7 7 Optional thermistor motor protection evaluation
Typical circuit diagrams 15.2 Control by pushbutton 15.2 Control by pushbutton 15.2.1 Control of the 3RW30 by pushbutton / ) 4 ,!! ,!! ,!! 6 0RWRU VWDUW 4 21 / / / 7 7 7 8 9 : 4 5: 6 0RWRU VWRS 6WDUW 0 $ 4 $ 0 1 Figure 15-2 Wiring of the 3RW30 control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data (Page 127) .
Typical circuit diagrams 15.2 Control by pushbutton 15.2.
Typical circuit diagrams 15.2 Control by pushbutton For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation (Page 175).
Typical circuit diagrams 15.3 Control by switch 15.3 Control by switch 15.3.1 Control of the 3RW30 by switch / ) 4 ,!! 4 ,!! ,!! 6 21 / / / 7 7 7 4 $ 4 $ 6WDUW 5: 8 0 1 Figure 15-5 9 : + 0 Wiring of the control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data (Page 127) . WARNING (2) Automatic restart.
Typical circuit diagrams 15.3 Control by switch 15.3.
Typical circuit diagrams 15.3 Control by switch (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data (Page 127) . WARNING (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command if a start command is still present.
Typical circuit diagrams 15.4 Control in automatic mode 15.4 Control in automatic mode 15.4.1 Control of the 3RW30 in automatic mode / ) 4 ,!! ,!! ,!! 4 6 21 2)) 21 / / / 7 7 7 8 9 : 4 $ 4 $ 6WDUW 5: + 1 0 Figure 15-8 0 Wiring of the 3RW30 control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data (Page 127) .
Typical circuit diagrams 15.4 Control in automatic mode 15.4.
Typical circuit diagrams 15.4 Control in automatic mode (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data (Page 127) . WARNING (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command if a start command is still present.
Typical circuit diagrams 15.5 Control by PLC 15.5 Control by PLC 15.5.1 Control of the 3RW30 with 24 V DC by PLC 9 '& / ) 4 3/& 2XWSXW 29(5/2$' 21 ,!! 4 ,!! ,!! 4 / / / 7 7 7 8 9 : 4 5: 3/& ,QSXW 0 $ 4 $ 6WDUW 0 0 Figure 15-11 Wiring of the 3RW30 control and main circuits (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data (Page 127) .
Typical circuit diagrams 15.5 Control by PLC 15.5.2 Control of the 3RW40 by PLC 9 '& / ) 4 . 5(6(7 ! V ,!! %<3$66(' 21 581 29(5/2$' )$,/85( 4 ,!! ,!! 4 4 / / / 7 7 7 8 9 : 9 '& 3/& 2XWSXW 0 3/& ,QSXW $ 4 $ 0 6WDUW 0 . 1 &RXSOLQJ UHOD\ FRQWURO IRU 5(6(7 ! VHF Figure 15-12 Wiring of the 3RW40 2 to 3RW40 4 control circuit (with 24 V control voltage) and the 3RW40 2 to 3RW40 7 main circuit /
Typical circuit diagrams 15.5 Control by PLC (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data (Page 127) . WARNING (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command if a start command is still present.
Typical circuit diagrams 15.6 Control with an optional main / line contactor 15.6 Control with an optional main / line contactor 15.6.
Typical circuit diagrams 15.6 Control with an optional main / line contactor 15.6.
Typical circuit diagrams 15.6 Control with an optional main / line contactor (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data (Page 127) . WARNING (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g.
Typical circuit diagrams 15.7 Reversing circuit 15.7 Reversing circuit 15.7.1 3RW30 reversing circuit / ) ) 4 ,!! ,!! ,!! . 4 21 4 6 6 0RWRU &: 4 6 6 6 6 0RWRU 0RWRU 0RWRU &&: 4 &: &&: 4 . / / / 7 7 7 8 9 : 4 5: 4 4 6 0RWRU VWRS $ 4 $ 6WDUW 0 8 8 $ 4 $ $ 4 $ $ .
Typical circuit diagrams 15.7 Reversing circuit (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data (Page 127) 15.7.2 / 3RW40 reversing circuit ) 4 ,!! ,!! ,!! %<3$66(' 21 581 4 .
Typical circuit diagrams 15.7 Reversing circuit / ) 6 5(6(7 WR V %<3$66(' 6 6 6 6 0RWRU 0RWRU 0RWRU 4 &&: &&: &: 6 6 0RWRU 4 &: + 4 $ $ 4 8 4 $ 0RWRU &: $ )DXOW 1 ( 4 ( 6WDUW 58 $ UHPRWH 5(6(7 4 $ $ . 6 0RWRU VWRS 8 . $ 8 $ 0RWRU &&: .
Typical circuit diagrams 15.8 Control of a magnetic parking brake 15.8 Control of a magnetic parking brake 15.8.
Typical circuit diagrams 15.8 Control of a magnetic parking brake 15.8.
Typical circuit diagrams 15.8 Control of a magnetic parking brake 15.8.
Typical circuit diagrams 15.9 Emergency stop 15.9 Emergency stop 15.9.1 3RW30 emergency stop and 3TK2823 safety relay / b9b'& 6 2Q 7. UHVHW 4 6 (PHUJHQF\ VWRS 4 < < < < < $ < 7.
Typical circuit diagrams 15.9 Emergency stop (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data (Page 127) . WARNING (2) Automatic restart. Can result in death, serious injury, or property damage. - If the 3TK28 is reset Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to chapter 3RW30: LEDs and troubleshooting (Page 48)) are automatically reset when the system returns to normal.
Typical circuit diagrams 15.9 Emergency stop / ) 4 %<3$66(' 21 581 6 6WDUW VWRS 5: ,!! ,!! 6WDUW / / / 7 7 7 4 5: 4 4 4 4 4 $ 4 $ ,!! 4 29(5/2$' )$,/85( 6 5(6(7 ! V 4 8 + + 0 9 : 0 1 )DXOW 1R FRQWURO YROWDJH 5: (PHUJHQF\ VWRS Figure 15-26 Wiring of the 3RW40 2 to 3RW40 4 control circuit and the 3RW40 2 to 3RW40 7 main circuit (1) For the permissible values for the m
Typical circuit diagrams 15.9 Emergency stop 15.9.3 3RW40 5 to 3RW40 7 emergency stop and 3TK2823 safety relay / b9b'& 6 2Q 7. 5(6(7 4 6 (PHUJHQF\ VWRS 4 < < < < < $ < 7.
Typical circuit diagrams 15.9 Emergency stop (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data (Page 127) . WARNING (2) Automatic restart. Can result in death, serious injury, or property damage. The start command (e.g. issued by the PLC or switch S1) must be reset prior to issuing a RESET command because the motor attempts to restart again automatically following this RESET command (3TK or 3RW) if a start command is still present.
Typical circuit diagrams 15.10 3RW and contactor for emergency starting 15.10 3RW and contactor for emergency starting 15.10.
Typical circuit diagrams 15.10 3RW and contactor for emergency starting 15.10.
Typical circuit diagrams 15.
Typical circuit diagrams 15.11 Dahlander / multispeed motor 15.11 Dahlander / multispeed motor 15.11.1 3RW30 and Dahlander motor starting / 4 4 ) )RU PRWRU RYHUORDG SURWHFWLRQ VHW UDWHG FXUUHQW IRU KLJK VSHHG 4 4 ) 4 ,!! ,!! ,!! 21 )RU PRWRU RYHUORDG SURWHFWLRQ VHW UDWHG FXUUHQW IRU ORZ VSHHG . 4 8 9 : 0 8 9 : 4 4 4 $ . $ $ 4 $ $ 4 $ 0DLQ FRQWDFWRU KLJK VSHHG $X[LOLDU\ FRQWDFWRU IRU VZ
Typical circuit diagrams 15.11 Dahlander / multispeed motor (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data (Page 127) . WARNING (2) Automatic restart. Can result in death, serious injury, or property damage. Faults caused by incorrect control voltage, a missing load, or a phase failure (refer to chapter 3RW30: LEDs and troubleshooting (Page 48)) are automatically reset when the system returns to normal.
Typical circuit diagrams 15.11 Dahlander / multispeed motor 15.11.2 4 4 6 5(6(7 ! V ) 4 ,!! ,!! ,!! 4 %<3$66(' ) 21 581 / 3RW40 2 to 3RW40 4 and Dahlander motor starting )RU PRWRU RYHUORDG SURWHFWLRQ VHW UDWHG FXUUHQW IRU KLJK VSHHG 6 6WDUW /RZ VSHHG / / 7 7 7 4 5: 6 0RWRU VWRS / 4 )RU PRWRU RYHUORDG SURWHFWLRQ VHW UDWHG FXUUHQW IRU ORZ VSHHG .
Typical circuit diagrams 15.11 Dahlander / multispeed motor (3) Alternatively, the motor feeder can be assembled as a fuseless or fused version with type of coordination 1 or 2. For the assignment of fuses and switching devices, refer to chapter Technical data (Page 127) For the optional thermistor motor protection evaluation, refer to Typical circuit for the optional thermistor motor protection evaluation (Page 175). NOTICE No soft stop possible. Set the ramp-down time to 0 s with the potentiometer. 15.
Typical circuit diagrams 15.11 Dahlander / multispeed motor 4 ,!! )RU PRWRU RYHUORDG SURWHFWLRQ VHW UDWHG FXUUHQW IRU KLJK VSHHG ,!! ,!! / / / 7 7 7 4 5: 4 )RU PRWRU RYHUORDG SURWHFWLRQ VHW UDWHG FXUUHQW IRU ORZ VSHHG 4 ) ] % 5% 8 9 : 4 0 8 0 9 : Figure 15-35 Wiring of the 3RW40 5 to 3RW40 7 main circuit (1) For the permissible values for the main and control voltage (dependent on the MLFB), refer to chapter Technical data (Page 127) .
Typical circuit diagrams 15.
16 Accessories 16.1 Box terminal blocks for soft starters For soft starter type Size Version Order No. Box terminal blocks for soft starters for round and ribbon cables (2 required per device) 3RW40 5. S6 • • Max. 70 mm2 Max. 120 mm2 3RT19 55-4G 3RT19 56-4G Auxiliary conductor terminal for box terminal 3RW40 7. S12 • Max. 240 mm2 3TX7 500-0A 3RT19 66-4G With auxiliary conductor terminal 16.2 3-phase infeed terminals 3-phase infeed terminals Connection cross-sections 16.
Accessories 16.4 Covers for soft starters 16.4 Covers for soft starters For soft starter type Size Order No. Terminal covers for box terminals Additional touch protection to be fitted at the box terminals (2 units required per device) 3RW30 3. S2 3RT19 36-4EA2 S3 3RT19 46-4EA2 3RW40 5. S6 3RT19 56-4EA2 3RW40 7. S12 3RT19 66-4EA2 3RW40 3. 3RW30 4. 3RW40 4.
Accessories 16.5 Modules for RESET 16.5 Modules for RESET For soft starter type Size Version Order No. Modules for remote RESET, electrical Operating range 0.85 to 1.1 x Us, Power consumption AC 80 VA, DC 70 W, ON time 0.2 s to 4 s, Switching frequency 60/h 3RW40 5. and 3RW40 7. S6, S12 • AC/DC 24 V ... 30 V 3RU19 00-2AB71 • AC/DC 110 V ... 127 V 3RU19 00-2AF71 • AC/DC 220 V ...
Accessories 16.6 Link modules to 3RV10 motor starter protectors 16.6 Link modules to 3RV10 motor starter protectors For soft starter type Size Motor starter protector size Order No. 3RW30 13, 3RW30 14, 3RW30 16, 3RW30 17, 3RW30 18 S00 S0 3RA19 21-1A 3RW30 26 S0 S0 3RA19 21-1A S2 S2 3RA19 31-1A S3 S3 3RA19 41-1A Link modules to 3RV10 motor starter protectors 3RW40 24 3RW40 26 3RW30 36 3RW40 36 3RW30 46, 3RW30 47 3RW40 46, 3RW40 47 16.
Accessories 16.8 Optional fan to increase the switching frequency (3RW40 2. to 3RW40 4.). 16.8 Optional fan to increase the switching frequency (3RW40 2. to 3RW40 4.). For soft starter type Size Order No. Fan (to increase the switching frequency and for device mounting in positions different from the normal position) 16.9 16.10 3RW40 2. S0 3RW49 28-8VB00 3RW40 3., 3RW40 4 S2, S3 3RW49 47-8VB00 Spare parts for fans (3RW40 5., 3RW40 7.
Accessories 16.
A Appendix A.1 Configuration data Configuration data Siemens AG Technical Support Low-Voltage Control Systems Phone: +49 (0) 911-895-5900 Fax: +49 (0) 911-895-5907 e-mail: technical-assistance@siemens.com 1.
Appendix A.1 Configuration data 1. Load data Load type (e.g. pump, mill etc.): Rated speed: rpm Rated torque or rated output Nm or kW Mass moment of inertia (load-specific) kg*m2 Mass moment of inertia (motor-specific) kg*m2 Speed / torque characteristic curve (The speed increments of the value pairs do not have to be equal) nL 1/m "nsyn" ML / MB 1.
5:BBBB BB%BB 5:BBBB BB%BB 5:BBBB BB%BB 5:BBBB BB%BB 5:BBBB BB%BB 3XPS ;<= 5: 7% 3ODQW LGHQWLILHU 5:BBBB BB%BB ,QVWDOOHG 5: W\SH 8 8 8 8 8 8 8 8 VWDUWLQJ 8 V V V V V V V W W W W W W W V W W UDPS XS V V V V
Appendix A.3 Correction sheet A.3 Correction sheet TO FROM (please complete): SIEMENS AG Name A&D CD MM3 Company / Department 92220 Amberg / Germany Address Phone Fax: 0 96 21 / 80-33 37 Fax System Manual for SIRIUS 3RW30 / 3RW40 soft starters Have you noticed any errors while reading this manual? If so, please use this form to tell us about them. We welcome comments and suggestions for improvement.
Index 3 3RW44, 15, 28, 102 3RW44 soft starter, 15, 28, 102 A Accessories, 211 Box terminal block, 211 Ambient temperature, 85 Application examples, 81 Heavy-duty starting, 83 Normal starting, 82 Applications, 23 For current limiting, 31 Soft stop, 33 Assembly type, 86, 90 ATEX, 34, 141 B Box terminal block, 211 Bypass contacts, 102, 110, 115 Bypass mode, 20 BYPASSED function, 46 C Capacitors, 67 CLASS 10, 81, 82, 113 CLASS 15, 113 CLASS 20, 83, 113 CLASS potentiometer, 112 CLASS setting, 34, 36, 112 Comm
Index N S Natural stop, 32 Normal starting, 77, 82, 129, 143, 145, 147, 149, 151 Ambient temperature, 82 General conditions and constraints, 82 Installation altitude, 82 ON time, 82 Parameter settings, 82 Safety rules, 14, 62 Screw-type technology, 69 Selection criteria, 23 Semiconductor fuses, 37 Side-by-side assembly, 59 SIRIUS 3RW44 soft starter, 15, 28, 102 SIRIUS modular system, 25 SITOR, 37 SITOR semiconductor fuses, 37 Soft start, 19, 100, 107 Soft stop, 19, 111 Spring-loaded technology, 69 Stand
Index V Voltage ramp, 27, 29, 100, 107, 108 W Water hammer, 33 Win-Soft Starter, 92 Win-Soft Starter software, 92 X xIe potentiometer, 110 SIRIUS 3RW30 / 3RW40 Manual, 10/2010, 535199502000 DS 03 223
Index 224 SIRIUS 3RW30 / 3RW40 Manual, 10/2010, 535199502000 DS 03
Service & Support Download catalogs and information material: www.siemens.com/industrial-controls/catalogs Newsletter – always up to date: www.siemens.com/industrial-controls/newsletter E-business in the Industry Mall: www.siemens.com/industrial-controls/mall Online-Support: www.siemens.com/industrial-controls/support Contact for all technical information: Technical Assistance Tel.: +49 (911) 895-5900 e-mail: technical-assistance@siemens.com www.siemens.