Data Sheet
Relative positive tolerance of the control supply
voltage at AC at 60 Hz
% 20
Control supply voltage 1 at DC rated value V 24
Relative negative tolerance of the control supply
voltage at DC
% -20
Relative positive tolerance of the control supply
voltage at DC
% 20
Display version for fault signal red
Mechanical data
Size of engine control device S00
Width mm 45
(height) mm 95
Depth mm 150
(mounting type) screw and snap-on mounting
(mounting position) With vertical mounting surface +/-10° rotatable, with
vertical mounting surface +/- 10° tiltable to the front
and back
Required spacing with side-by-side mounting
● upwards
mm 60
● at the side
mm 15
● downwards
mm 40
Wire length maximum m 300
Number of poles for main current circuit 3
Connections/Terminals
Type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control current circuit
screw-type terminals
Number of NC contacts for auxiliary contacts 0
Number of NO contacts for auxiliary contacts 1
Number of CO contacts for auxiliary contacts 0
Type of connectable conductor cross-sections for
main contacts for box terminal using the front
clamping point
● solid
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
● finely stranded with core end processing
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
Type of connectable conductor cross-sections at
AWG conductors for main contacts for box terminal
● using the front clamping point
2x (16 ... 10)
Type of connectable conductor cross-sections for
auxiliary contacts
● solid
2x (0.25 ... 2.5 mm²)
● finely stranded with core end processing
2x (0.25 ... 1.5 mm²)
3RW30 18-1BB04 Subject to change without notice
Page 3/
6
09/12/2019 © Copyright Siemens