Data Sheet
Data sheet 3RV2311-1HC20
Circuit breaker size S00 for starter combination Rated current 8 A N-
release 104 A Spring-type terminal Standard switching capacity
Product brand name SIRIUS
Product designation Circuit breaker
Design of the product For starter combinations
Product type designation 3RV2
General technical data
Size of the circuit-breaker S00
Size of contactor can be combined company-specific S00, S0
Product extension
● Auxiliary switch
Yes
Power loss [W] for rated value of the current
● at AC in hot operating state per pole
3.1W
Insulation voltage with degree of pollution 3 rated
value
690V
Surge voltage resistance rated value 6kV
maximum permissible voltage for safe isolation
● in networks with grounded star point between
main and auxiliary circuit
400V
● in networks with grounded star point between
main and auxiliary circuit
400V