Data Sheet
Protection class IP
● on the front
IP20
● of the terminal
IP00
Shock resistance
● acc. to IEC 60068-2-27
25g / 11 ms Sinus
Mechanical service life (switching cycles)
● of the main contacts typical
25000
● of auxiliary contacts typical
25000
Electrical endurance (switching cycles)
● typical
25000
Type of protection according to ATEX directive
2014/34/EU
Ex II (2) GD
Certificate of suitability according to ATEX directive
2014/34/EU
DMT 02 ATEX F 001
Protection against electrical shock finger-safe when touched vertically from front acc. to IEC 60529
Reference code acc. to DIN EN 81346-2 Q
Ambient conditions
Installation altitude at height above sea level
● maximum
2000m
Ambient temperature
● during operation
-20...+60°C
● during storage
-50...+80°C
● during transport
-50...+80°C
Temperature compensation -20...+60°C
Relative humidity during operation 10...95%
Main circuit
Number of poles for main current circuit 3
Adjustable pick-up value current of the current-
dependent overload release
28...40A
Operating voltage
● rated value
690V
● at AC-3 rated value maximum
690V
Operating frequency rated value 50...60Hz
Operating current rated value 40A
Operating current
● at AC-3
— at 400 V rated value
40A
Operating power
● at AC-3
— at 230 V rated value
11000W
— at 400 V rated value
18500W
— at 500 V rated value
22000W
3RV2041-4FA10 Subject to change without notice