Datasheet
Operational short-circuit current breaking capacity
(Ics) at AC
● at 240 V rated value
100A
● at 400 V rated value
30kA
● at 500 V rated value
5kA
● at 690 V rated value
2kA
Maximum short-circuit current breaking capacity (Icu)
● at AC at 240 V rated value
100kA
● at AC at 400 V rated value
65kA
● at AC at 500 V rated value
10kA
● at AC at 690 V rated value
4kA
Response value current of the instantaneous short-
circuit release
650A
UL/CSA ratings:
Full-load current (FLA) for three-phase AC motor
● at 480 V rated value
45A
● at 600 V rated value
45A
● yielded mechanical performance [hp] for single-
phase AC motor
— at 110/120 V rated value
3hp
— at 230 V rated value
10hp
● Yielded mechanical performance [hp] for three-
phase AC motor
— at 200/208 V rated value
15hp
— at 220/230 V rated value
15hp
— at 460/480 V rated value
40hp
— at 575/600 V rated value
50hp
Short-circuit protection
Design of the short-circuit trip magnetic
Design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 240 V
none required
● at 400 V
125
● at 500 V
100
● at 690 V
80
Installation/ mounting/ dimensions:
Mounting position any
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
Height 140mm
Width 55mm
Depth 149mm
3RV2031-4VA10 Changes preserved
Page 3/
6
26.02.2016 © Copyright Siemens AG