Data Sheet

● at 400 V
gG 63 A
● at 500 V
gG 63 A
● at 690 V
gG 63 A
Installation/ mounting/ dimensions
Mounting position any
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
Height 97mm
Width 45mm
Depth 97mm
Required spacing
● with side-by-side mounting
— forwards
0mm
— Backwards
0mm
— upwards
50mm
— downwards
50mm
— at the side
0mm
● for grounded parts
— forwards
0mm
— Backwards
0mm
— upwards
50mm
— at the side
30mm
— downwards
50mm
● for live parts
— forwards
0mm
— Backwards
0mm
— upwards
50mm
— downwards
50mm
— at the side
30mm
Connections/ Terminals
Product function
● removable terminal for auxiliary and control
circuit
No
Type of electrical connection
● for main current circuit
screw-type terminals
Arrangement of electrical connectors for main current
circuit
Top and bottom
Type of connectable conductor cross-sections
● for main contacts
— single or multi-stranded
2x (1 ... 2,5 mm²), 2x (2,5 ... 10 mm²)
— finely stranded with core end processing
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
3RV2021-4EA10-0BA0 Subject to change without notice
Page 4/
8
09/13/2019 © Copyright Siemens