Datasheet

Arrangement of electrical connectors for main current
circuit
Top and bottom
Type of connectable conductor cross-section
● for main contacts
— single or multi-stranded
2x (1 ... 2,5 mm²), 2x (2,5 ... 10 mm²)
— finely stranded with core end processing
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
● for AWG conductors for main contacts
2x (16 ... 12), 2x (14 ... 8)
Design of screwdriver shaft Diameter 5 to 6 mm
Design of the thread of the connection screw
● for main contacts
M4
Safety related data:
B10 value with high demand rate acc. to SN 31920 50000
Proportion of dangerous failures
● with low demand rate acc. to SN 31920
40%
● with high demand rate acc. to SN 31920
40%
T1 value for proof test interval or service life acc. to
IEC 61508
10y
Protection against electrical shock finger-safe
Mechanical data:
Size of the circuit-breaker S0
Ambient conditions:
Installation altitude at height above sea level
maximum
2000m
Ambient temperature
● during operation
-20...+60°C
● during storage
-50...+80°C
● during transport
-50...+80°C
Relative humidity during operation 10...95%
Display:
Display version
● for switching status
Handle
Certificates/ approvals:
3RV2021-4CA10 Changes preserved
Page 4/
7
27.04.2015 © Copyright Siemens AG