Data Sheet

● for three-phase AC motor
— at 200/208 V rated value
1hp
— at 220/230 V rated value
1hp
— at 460/480 V rated value
3hp
— at 575/600 V rated value
3hp
Contact rating of auxiliary contacts according to UL C300 / R300
Short-circuit protection
Product function Short circuit protection Yes
Design of the short-circuit trip magnetic
Design of the fuse link
● for short-circuit protection of the auxiliary switch
required
fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current
Ik < 400 A)
Design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 400 V
gG 32 A
● at 500 V
gG 32 A
● at 690 V
gG 25 A
Installation/ mounting/ dimensions
Mounting position any
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
Height 97mm
Width 45mm
Depth 97mm
Required spacing
● with side-by-side mounting
— forwards
0mm
— Backwards
0mm
— upwards
50mm
— downwards
50mm
— at the side
0mm
● for grounded parts
— forwards
0mm
— Backwards
0mm
— upwards
50mm
— at the side
30mm
— downwards
50mm
● for live parts
— forwards
0mm
— Backwards
0mm
— upwards
50mm
3RV2011-1FA15-0BA0 Subject to change without notice
Page 4/
9
09/12/2019 © Copyright Siemens