Data Sheet
Width 45mm
Depth 97mm
Required spacing
● with side-by-side mounting
— forwards
0mm
— Backwards
0mm
— upwards
50mm
— downwards
50mm
— at the side
0mm
● for grounded parts
— forwards
0mm
— Backwards
0mm
— upwards
50mm
— at the side
30mm
— downwards
50mm
● for live parts
— forwards
0mm
— Backwards
0mm
— upwards
50mm
— downwards
50mm
— at the side
30mm
Connections/ Terminals
Product function
● removable terminal for auxiliary and control
circuit
No
Type of electrical connection
● for main current circuit
Ring cable lug connection
● for auxiliary and control current circuit
ring cable connection
Arrangement of electrical connectors for main current
circuit
Top and bottom
Tightening torque
● for main contacts for ring cable lug
0.8...1.2N·m
● for auxiliary contacts for ring cable lug
1.2...0.8N·m
Outer diameter of the usable ring cable lug maximum 7.5mm
Design of screwdriver shaft Diameter 5 to 6 mm
Size of the screwdriver tip Size 2 and Pozidriv2
Design of the thread of the connection screw
● for main contacts
M3
● of the auxiliary and control contacts
M3
Safety related data
B10 value
3RV2011-0FA40 Subject to change without notice
Page 4/
8
09/12/2019 © Copyright Siemens