Datasheet

backwards
upwards
mm 50
sidewards
mm 30
downwards
mm 50
Distance, to be maintained, conductive elements
forwards
mm 0
backwards
mm 0
upwards
mm 50
downwards
mm 50
sidewards
mm 30
Connections:
Product function
removable terminal for main circuit
No
removable terminal for auxiliary and control
circuit
No
Design of the electrical connection
for main current circuit
screw-type terminals
Type of the connectable conductor cross-section
for main contacts
solid
2x (0.75 ... 2.5 mm²), 2x 4 mm²
finely stranded
with conductor end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
for AWG conductors / for main contacts
2x (18 ... 14), 2x 12
Certificates/approvals:
Verification of suitability
CE / UL / CSA
für Staubexplosionsschutz für Zone 21/22
no
for gas explosion protection for zone 1/2
no
General Product Approval For use in hazardous locations
CCC
CSA
GOST
UL
ATEX
-EC-
Type
Test Certificates
other Special Test
Certificate
Type Test
Certificates/Test
Report
Shipping Approval
ABS
(
American Bureau of Shipping
GL /
Germanischer Lloyd
LRS /
Lloyds Register of Shipping
PRS /
Polski Rejestr Statkow
RINA /
Registro Italiano Navale
RMRS /
Russian Maritime Register
other
Household and similar appliances
Declaration of
Conformity
other
UL/CSA ratings
yielded mechanical performance (hp)
for single-phase squirrel cage motors
at 110/120 V / rated value
hp 0.5
at 230 V / rated value
hp 1.5
for three-phase squirrel cage motors
at 200/208 V / rated value
hp 2
at 220/230 V / rated value
hp 3
at 460/480 V / rated value
hp 5
at 575/600 V / rated value
hp 7.5
Operating current (FLA) / for three-phase squirrel cage
motors
A 7.6
http://support.automation.siemens.com/WW/view/en/33243658&td=1