Datasheet

3RV Motor Starter Protectors/Circuit Breakers up to 100 A
27
Siemens · 2010
Accessories
Mountable accessories
Technical specifications
Front transverse auxiliary switches
Switching capacity for different voltages
1 CO contact 1 NO + 1 NC, 2 NO
Rated operational current I
e
At AC-15, alternating voltage
-24 V A 4 2
-230 V A
3 0.5
-400 V A
1.5 --
-690 V A
0.5 --
At AC-12 = I
th
, alternating voltage
-24 V A 10 2.5
-230 V A
10 2.5
-400 V A
10 --
-690 V A
10 --
At DC-13, direct voltage L/R 200 ms
-24 V A 1 1
-48 V A
-- 0.3
-60 V A
-- 0.15
-110 V A
0.22 --
-220 V A
0.1 --
Minimum load capacity V
17
mA
1
Front transverse solid-state compatible auxiliary switches
1 CO contact
Rated operational voltage U
e
Alternating voltage V 250
Rated operational current I
e
/AC-14 at U
e
= 250 V A 0.5
Rated operational current I
e
/AC-14 at U
e
= 125 V A 1
Rated operational voltage U
e
Direct voltage L/R 200 ms V 250
Rated operational current I
e
/DC-13 at U
e
= 250 V A 0.27
Rated operational current I
e
/DC-13 at U
e
= 125 V A 0.44
Minimum load capacity V
5
mA
1
Lateral auxiliary switches with signal switch
Switching capacity for different voltages:
Lateral auxiliary switch with 1 NO + 1 NC, 2 NO, 2 NC, 2 NO + 2 NC;
signal switch
Rated operational current I
e
At AC-15, alternating voltage
-24 V A 6
-230 V A
4
-400 V A
3
-690 V A
1
At AC-12 = I
th
, alternating voltage
-24 V A 10
-230 V A
10
-400 V A
10
-690 V A
10
At DC, direct voltage L/R 200 ms
-24 V A 2
-110 V A
0.5
-220 V A
0.25
-440 V A
0.1
Minimum load capacity V
17
mA
1
Auxiliary trip units
Undervoltage trip units Shunt trip units
Power consumption
During pick-up
- AC voltages VA/W 20.2/13 20.2/13
- DC voltages W
20 13 ... 80
During uninterrupted duty
- AC voltages VA/W 7.2/2.4 --
- DC voltages W
2.1 --
Response voltage
Tripping V 0.35 ... 0.7 x U
s
0.7 ... 1.1 x U
s
•Pickup V 0.85 ... 1.1 x U
s
--
Maximum opening time ms
20