Datasheet

3RV Motor Starter Protectors/Circuit Breakers up to 100 A
25
Siemens · 2010
General data
Schematics
Internal circuit diagrams
Switching examples
Note:
When using the NO contact to connect the voltage transformer
circuit breaker, the binary input of the distance protection device
(Siemens 7 SA xxx) should be set to "active without voltage".
This connection type is used for additional monitoring of correct
wiring.
More information
Conversion of voltage transformer circuit breakers 3VU13 to 3RV1
The 3VU13 voltage transformer motor starter protectors previ-
ously available have been discontinued. The 3RV1 voltage
transformer motor starter protectors are offered as replacement
types.
Motor starter protector/
circuit breaker
3RV10 ..,
3RV14 ..,
3RV16 11-0BD10,
3RV17 ..,
3RV18 ..
Motor starter protector with overload
relay function
3RV11 ..
Motor starter protector
3RV13 ..
Voltage transformer circuit breaker
3RV16 11-1.G14
1 3 5
4 62
N S B 0 _ 0 0 0 0 8 a
v
v
v
T 2 T 3
T 1
L 1 L 2 L 3
1 3 5
4 62
T 2 T 3
T 1
L 1 L 2 L 3
N S B 0 _ 0 0 0 0 9 b
9 7
9 8
9 5
9 6
v
v
v
T E S T
1 3 5
4 62
N S B 0 _ 0 0 0 1 0 a
T 2 T 3
T 1
L 1 L 2 L 3
v
v
v
135
462
14
11
12
NSB0_01105b
1
v
1
v
1
v
Distance protection
and starting
Starting
from voltage transformer unit
3RV11 motor starter protector with overload relay function
Q1
OFF ButtonS1
ON ButtonS2
Self-holding contactK1
Fuse (gL/gG) 6 AF1, F2
Undervoltage trip unit 3RV11Q1
L1
N(L2)
F1
F2
NSB0_00025c
S1
S2
K1
K1
3RV16 11-1.G14 voltage transformer circuit breaker
12
14
11
+
NSB0_01106b
D i s t a n c e p r o t e c t i o n
B I
( b i n a r y
i n p u t )
V o l t a g e t r a n s f o r m e r
c i r c u i t b r e a k e r r e l e a s e d
( a c t i v e
w i t h o u t v o l t a g e )
Previous type Replacement type
3VU13 11-6HR00 3RV16 11-1CG14
3VU13 21-6HR00 3RV16 11-1CG14 + 3RV19 01-1A
3VU13 11-6JR00 3RV16 11-1DG14