Datasheet

3RV Motor Starter Protectors/Circuit Breakers up to 100 A
General data
16
Siemens · 2010
Permissible rated data of devices approved for North America (UL/CSA)
Motor starter protectors of the 3RV1 series are approved for
UL/CSA and according to UL 508 and CSA C22.2 No. 14 they
can be used on their own or as a load feeder in combination with
a contactor.
These motor starter protectors can be used as "Manual Motor
Controllers" for "Group Installations", as "Manual Motor Control-
lers Suitable for Tap Conductor Protection in Group Installations"
and as "Self-Protected Combination Motor Controllers" (Type E).
3RV1 motor starter protectors as "Manual Motor Controllers"
If used as a "Manual Motor Controller", the motor starter protector
is always operated in combination with an upstream short-circuit
protection device. Approved fuses or a circuit breaker accor-
ding to UL 489/CSA C22.2 No. 5-02 can be used. These devices
must be dimensioned according to the National Electrical Code
(UL) or Canadian Electrical Code (CSA).
Approval of the 3RV as a Manual Motor Controller can be found
under the following file numbers:
UL File No. 47705, CCN: NLRV,
CSA Master Contract 165071, Product Class: 3211 05.
1) hp rating = Power rating in horse power (maximum motor rating).
2) FLA = Full Load Amps/Motor full load current.
3) Complies with "short-circuit breaking capacity" according to UL/CSA.
Motor starter
protectors
hp rating
1)
for FLA
2)
max.
Rated current
I
n
240 V AC 480 V AC 600 V AC
UL CSA UL CSA UL CSA
I
bc
3)
I
bc
3)
I
bc
3)
I
bc
3)
I
bc
3)
I
bc
3)
Type V 1-phase 3-phase A kA kA kA kA kA kA
Size S00
3RV10 11, 3RV16 11-0BD10 0.16 ... 2 65 65 65 65 10 10
2.5 65 65 65 65 10 10
FLA
2)
max. 12 A, 115 1/2 -- 3.2 65 65 65 65 10 10
600 V
200 1 1/2 3
4 65 65 65 65 10 10
NEMA size 00
230 2 3 5 65 65 65 65 10 10
460 -- 7 1/2 6.3 65 65 65 65 10 10
575/600 -- 10
8 65 65 65 65 10 10
10 65 65 65 65 10 10
12 65 65 65 65 10 10
Size S0
3RV10 21/3RV11 21, 3RV13 21 0.16 ... 3.2 65 65 65 65 30 30
4 65 65 65 65 30 30
FLA
2)
max. 25 A, 115 2 -- 5 65 65 65 65 30 30
600 V
200 3 5
6.3 65 65 65 65 30 30
NEMA size 1
230 3 7 1/2 8 65 65 65 65 30 30
460 -- 15 10 65 65 65 65 30 30
575/600 -- 20
12.5 65 65 65 65 30 30
16 65 65 65 65 10 10
20 65 65 65 65 10 10
22 65 65 65 65 10 10
25 65 65 65 65 10 10
Size S2
3RV10 31/3RV11 31, 3RV13 31 16 65 65 65 65 30 25
20 65 65 65 65 30 25
FLA
2)
max. 50 A, 115 3 -- 25 65 65 65 65 30 25
600 V
200 7 1/2 15
32 65 65 65 65 30 25
NEMA size 2
230 10 20 40 65 65 65 65 30 25
460 -- 40 45 65 65 65 65 30 25
575/600 -- 50 50 65 65 65 65 30 25
Size S3
3RV10 41/3RV10 42, 3RV11 42, 3RV13 41/3RV13 42 16 65 65 65 65 30 30
20 65 65 65 65 30 30
FLA
2)
max. 99 A, 115 7 1/2 -- 25 65 65 65 65 30 30
600 V
200 20 30
32 65 65 65 65 30 30
NEMA size 3
230 20 40 40 65 65 65 65 30 30
460 -- 75 50 65 65 65 65 30 30
575/600 -- 100
63 65 65 65 65 30 30
75 65 65 65 65 30 30
90 65 65 65 65 10 10
100 65 65 65 65 10 10