Datasheet
3RV Motor Starter Protectors/Circuit Breakers up to 100 A
General data
10
Siemens · 2010
■
Technical specifications
Short-circuit breaking capacity I
cu
, I
cs
acc. to IEC 60947-2
This table shows the rated ultimate short-circuit breaking
capacity I
cu
and the rated service short-circuit breaking
capacity I
cs
of the 3RV1 motor starter protectors with different
inception voltages dependent of the rated current I
n
of the motor
starter protectors.
Motor starter protector infeed is permissible at the upper or
lower terminals without restricting the rated data. If the short-cir-
cuit current at the place of installation exceeds the rated short-
circuit breaking capacity of the motor starter protector as speci-
fied in the table, a back-up fuse is required. Alternatively, a
motor starter protector with a limiter function can be connected
upstream.
The maximum rated current for the back-up fuse is specified in
the tables. The rated ultimate short-circuit breaking capacity
then applies as specified on the fuse.
Fuseless construction
Motor starter protector contactor combinations for short-circuit
currents up to 50 kA can be ordered in the form of fuseless load
feeders according to Chapter 6.
1) 10 % overvoltage.
2) 5 % overvoltage.
3) Back-up fuse only required if the short-circuit current at the place of
installation > I
cu
.
4) Alternatively, fuseless limiter combinations for 690 V AC can also be used.
5) The values for the 3RV17 42 circuit breakers have been tested only up to
400 V/415 V AC; values > 440 V AC on request.
Motor starter
protectors/circuit
breakers
Rated current
I
n
Up to 240 V AC
1)
Up to
400 V
1)
/415 V AC
2)
Up to
440 V
1)
/460 V AC
2)
Up to
500 V
1)
/525 V AC
2)
Up to 690 V AC
1)
(these values do not apply to 3RV17 42 circuit breakers)
I
cu
I
cs
Max. fuse
(gL/gG)
I
cu
I
cs
Max. fuse
(gL/gG)
3)
I
cu
I
cs
Max. fuse
(gL/gG)
3)
I
cu
I
cs
Max. fuse
(gL/gG)
3)
I
cu
I
cs
Max.
fuse
(gL/gG)
3)4)
Type A kA kA A kA kA A kA kA A kA kA A kA kA A
Size S00
3RV10, 0.16 ... 1 100 100 ° 100 100 ° 100 100 ° 100 100 ° 100 100 °
3RV16 11-0BD10
1.25; 1.6 100 100 ° 100 100 ° 100 100 ° 100 100 ° 2220
2; 2.5 100 100 ° 100 100 ° 100 100 ° 101035 2 2 35
3.2; 4 100 100 ° 100 100 ° 50 10 40 3340 2240
5; 6.3 100 100 ° 100 100 ° 50 10 50 3350 2250
8 100 100 ° 53 12.5 80 50 10 63 3363 2263
10 100 100 ° 53 12.5 80 6463 3363 2263
12 100 100 ° 53 12.5 80 6480 3380 2280
Size S0
3RV1. 2,
3RV17 21,
3RV18 21
0.16 ... 1.6 100 100 ° 100 100 ° 100 100 ° 100 100 ° 100 100 °
2; 2.5 100 100 ° 100 100 ° 100 100 ° 100 100 ° 8825
3.2 100 100 ° 100 100 ° 100 100 ° 100 100 ° 8832
4; 5 100 100 ° 100 100 ° 100 100 ° 100 100 ° 6332
6.3 100 100 ° 100 100 ° 100 100 ° 100 100 ° 6350
8 100 100 ° 100 100 ° 50 25 63 42 21 63 6 3 50
10 100 100 ° 100 100 ° 50 25 80 42 21 63 6 3 50
12.5 100 100 ° 100 100 ° 50 25 80 42 21 80 6 3 63
16 100 100 ° 50 25 100 50 10 80 10 5 80 4 2 63
20 100 100 ° 50 25 125 50 10 80 10 5 80 4 2 63
22; 25 100 100 ° 50 25 125 50 10 100 10 5 80 4 2 63
Size S2
3RV1. 3 16 100 100 ° 50 25 100 50 25 100 12 6 63 5 3 63
20 100 100 ° 50 25 100 50 25 100 12 6 80 5 3 63
25 100 100 ° 50 25 100 50 15 100 12 6 80 5 3 63
32 100 100 ° 50 25 125 50 15 125 10 5 100 4 2 63
40; 45 100 100 ° 50 25 160 50 15 125 10 5 100 4 2 63
50 100 100 ° 50 25 160 50 15 125 10 5 100 4 2 80
Size S3
3RV1. 41 40 100 100 ° 50 25 125 50 20 125 12 6 100 6 3 63
50 100 100 ° 50 25 125 50 20 125 12 6 100 6 3 80
63 100 100 ° 50 25 160 50 20 160 12 6 100 6 3 80
75 100 100 ° 50 25 160 50 20 160 84125 53100
90; 100 100 100 ° 50 25 160 50 20 160 84125 53125
Size S3, with increased swit-
ching capacity
3RV1. 42 /
3RV17 42
5)
16/10 100 100 ° 100 50 ° 100 50 ° 301580 127 63
20/15 100 100 ° 100 50 ° 100 50 ° 301580 127 63
25/20 100 100 ° 100 50 ° 100 50 ° 301580 127 63
32/25 100 100 ° 100 50 ° 100 50 ° 2211100 127 63
40/30 100 100 ° 100 50 ° 100 50 °18916012680
50/35 ... 40 100 100 ° 100 50 ° 100 50 °157.5160105100
63/45 ... 50 100 100 ° 100 50 ° 70 50 200 15 7.5 160 7.5 4 100
75/60 100 100 ° 100 50 ° 70 50 200 10 5 160 6 3 125
90/70 100 100 ° 100 50 ° 70 50 200 10 5 160 6 3 160
100/ -- 100 100 ° 100 50 ° 70 50 200 10 5 160 6 3 160
Short-circuit resistant up to at least 50 kA
° No back-up fuse required, since short-circuit resistant up to 100 kA