Data Sheet

— upwards
10mm
— at the side
10mm
— downwards
10mm
● for live parts
— forwards
10mm
— Backwards
0mm
— upwards
10mm
— downwards
10mm
— at the side
10mm
Connections/ Terminals
Product function
● removable terminal for auxiliary and control
circuit
No
Type of electrical connection
● for main current circuit
screw-type terminals
● for auxiliary and control current circuit
spring-loaded terminals
Arrangement of electrical connectors for main current
circuit
Top and bottom
Type of connectable conductor cross-sections
● for main contacts
— single or multi-stranded
2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
— finely stranded with core end processing
2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
● at AWG conductors for main contacts
2x (18 ... 2), 1x (18 ... 1)
Type of connectable conductor cross-sections
● for auxiliary contacts
— single or multi-stranded
2x (0,5 ... 2,5 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²)
— finely stranded without core end
processing
2x (0.5 ... 2.5 mm²)
● at AWG conductors for auxiliary contacts
2x (20 ... 14)
Tightening torque
● for main contacts with screw-type terminals
3...4.5N·m
Design of screwdriver shaft Diameter 5 ... 6 mm
Size of the screwdriver tip Pozidriv PZ 2
Design of the thread of the connection screw
● for main contacts
M6
Safety related data
T1 value for proof test interval or service life acc. to
IEC 61508
20y
Display
Display version
3RU2136-4FD0 Subject to change without notice
Page 4/