Datasheet

Number of poles / for main current circuit
3
Operating voltage / at AC-3 / rated value
maximum
V 690
Operating current / at AC-3 / at 400 V
rated value
A 10
Service power / at AC-3
at 400 V / rated value
kW 4
at 500 V / rated value
kW 5.5
at 690 V / rated value
kW 7.5
Adjustable response current
of the current-dependent overload release
A 7…10
Operating current / of the fuse link / rated value
A 35
Auxiliary circuit:
Contact reliability / of the auxiliary contacts
< 1 error per 100 million operating cycles
Number of NC contacts / for auxiliary contacts
1
Number of NO contacts / for auxiliary contacts
1
Number of change-over switches / for auxiliary contacts
0
Operating current / of the auxiliary contacts
at AC-15
at 24 V
A 3
at 110 V
A 3
at 120 V
A 3
at 125 V
A 3
at 230 V
A 2
at 400 V
A 1
at DC-13
at 24 V
A 1
at 110 V
A 0.22
at 125 V
A 0.22
at 220 V
A 0.11
Short-circuit:
Design of the fuse link / for short-circuit protection of the
auxiliary switch / required
fuse gG: 10 A
Installation/mounting/dimensions:
Built in orientation
vertical
Type of mounting
direct mounting
Width
mm 45
Height
mm 87
Depth
mm 73
Distance, to be maintained, to the ranks assembly
forwards
mm 0
backwards
mm 0
upwards
mm 6
downwards
mm 6
sidewards
mm 6
Distance, to be maintained, to earthed part
forwards
mm 0
backwards
mm 0
upwards
mm 6
downwards
mm 6
sidewards
mm 6
Distance, to be maintained, conductive elements
forwards
mm 0
backwards
mm 0
http://support.automation.siemens.com/WW/view/en/33242293&td=1
Page 2 of 5 3/30/2012 12:39:24 PM