Datasheet

Control supply voltage at AC
● at 50 Hz rated value
24V
● at 60 Hz rated value
24V
Operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz
0.8...1.1
● at 60 Hz
0.85...1.1
Apparent pick-up power of magnet coil at AC 190V·A
● at 50 Hz
210V·A
● at 60 Hz
188V·A
Inductive power factor with closing power of the coil 0.72
● at 50 Hz
0.69
● at 60 Hz
0.65
Apparent holding power of magnet coil at AC 17.2V·A
● at 50 Hz
17.2V·A
● at 60 Hz
16.5V·A
Inductive power factor with the holding power of the
coil
0.36
● at 50 Hz
0.36
● at 60 Hz
0.39
Closing delay
● at AC
12...22ms
Opening delay
● at AC
10...18ms
Arcing time 10...20ms
Control version of the switch operating mechanism AC
Auxiliary circuit
Number of NC contacts for auxiliary contacts
● instantaneous contact
1
Number of NO contacts for auxiliary contacts
● instantaneous contact
1
Operating current at AC-12 maximum 10A
Operating current at AC-15
● at 230 V rated value
6A
● at 400 V rated value
3A
● at 500 V rated value
2A
● at 690 V rated value
1A
Operating current at DC-12
● at 24 V rated value
10A
● at 48 V rated value
6A
● at 60 V rated value
6A
● at 110 V rated value
3A