Data Sheet

Operating current at DC-13
● at 24 V rated value
10A
● at 48 V rated value
2A
● at 110 V rated value
1A
● at 125 V rated value
0.3A
● at 220 V rated value
0.3A
● at 600 V rated value
0.3A
Design of the miniature circuit breaker
● for short-circuit protection of the auxiliary switch
required
gG: 10 A (230 V, 400 A)
Contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
Contact rating of auxiliary contacts according to UL A600 / Q600
Short-circuit protection
Product function Short circuit protection No
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 80 A (690 V, 100 kA)
— with type of assignment 2 required
gG: 50 A (690 V, 100 kA)
● for short-circuit protection of the auxiliary switch
required
gG: 10 A (690 V, 1 kA)
Installation/ mounting/ dimensions
Mounting position +/-180° rotation possible on vertical mounting surface; can be
tilted forward and backward by +/- 22.5° on vertical mounting
surface
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
● Side-by-side mounting
Yes
Height 85mm
Width 45mm
Depth 97mm
Required spacing
● with side-by-side mounting
— forwards
10mm
— upwards
10mm
— downwards
10mm
— at the side
0mm
● for grounded parts
— forwards
10mm
— upwards
10mm
— at the side
6mm
— downwards
10mm
3RT2326-1AP00-4AA0 Subject to change without notice
Page 4/
8
09/12/2019 © Copyright Siemens