Datasheet
— at 575/600 V rated value
25hp
Contact rating of auxiliary contacts according to UL A600 / Q600
Short-circuit protection
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gG: 125A (690V,100kA), aM: 50A (690V,100kA), BS88: 125A
(415V,80kA)
— with type of assignment 2 required
gG: 50A (690V,100kA), aM: 25A (690V, 100kA), BS88: 50A
(415V, 80kA)
● for short-circuit protection of the auxiliary switch
required
fuse gG: 10 A
Installation/ mounting/ dimensions
Mounting position +/-180° rotation possible on vertical mounting surface; can be
tilted forward and backward by +/- 22.5° on vertical mounting
surface
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
● Side-by-side mounting
Yes
Height 102mm
Width 45mm
Depth 107mm
Required spacing
● with side-by-side mounting
— forwards
10mm
— upwards
10mm
— downwards
10mm
— at the side
0mm
● for grounded parts
— forwards
10mm
— upwards
10mm
— at the side
6mm
— downwards
10mm
● for live parts
— forwards
10mm
— upwards
10mm
— downwards
10mm
— at the side
6mm
Connections/Terminals
Type of electrical connection
● for main current circuit
spring-loaded terminals
● for auxiliary and control current circuit
spring-loaded terminals
Type of connectable conductor cross-sections
3RT2028-2BB40 Subject to change without notice
Page 6/
11
12/18/2018 © Copyright Siemens