Datasheet

— at 575/600 V rated value
20hp
Contact rating of auxiliary contacts according to UL A600 / Q600
Short-circuit protection
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required
gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 100 A
— with type of assignment 2 required
gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35 A
● for short-circuit protection of the auxiliary switch
required
fuse gL/gG: 10 A
Installation/ mounting/ dimensions:
Mounting position +/-180° rotation possible on vertical mounting surface; can be
tilted forward and backward by +/- 22.5° on vertical mounting
surface
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 50022
● Side-by-side mounting
Yes
Height 102mm
Width 45mm
Depth 154mm
Required spacing
● with side-by-side mounting
— forwards
0mm
— Backwards
0mm
— upwards
0mm
— downwards
0mm
— at the side
0mm
● for grounded parts
— forwards
0mm
— Backwards
0mm
— upwards
0mm
— at the side
6mm
— downwards
0mm
● for live parts
— forwards
0mm
— Backwards
0mm
— upwards
0mm
— downwards
0mm
— at the side
6mm
Connections/ Terminals:
Type of electrical connection
● for main current circuit
spring-loaded terminals
3RT2026-2KF40 Changes preserved
Page 6/
10
06.04.2016 © Copyright Siemens AG