Datasheet
— at 400 V rated value
23kW
— at 400 V at 60 °C rated value
23kW
— at 690 V rated value
40kW
— at 690 V at 60 °C rated value
40kW
● at AC-2 at 400 V rated value
11kW
● at AC-3
— at 230 V rated value
5.5kW
— at 400 V rated value
11kW
— at 690 V rated value
11kW
Operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value
4.4kW
● at 690 V rated value
7.7kW
Thermal short-time current limited to 10 s 200A
Power loss [W] at AC-3 at 400 V for rated value of
the operating current per conductor
1.6W
No-load switching frequency
● at DC
15001/h
Operating frequency
● at AC-1 maximum
10001/h
● at AC-2 maximum
7501/h
● at AC-3 maximum
7501/h
● at AC-4 maximum
2501/h
Control circuit/ Control:
Type of voltage of the control supply voltage DC
Control supply voltage at DC
● rated value
110V
Operating range factor control supply voltage rated
value of magnet coil at DC
0.7...1.25
Design of the surge suppressor with varistor
Closing power of magnet coil at DC 4.5W
Holding power of magnet coil at DC 4.5W
Closing delay
● at DC
50...170ms
Opening delay
● at DC
15...17.5ms
Arcing time 10...10ms
Residual current of the electronics for control with
signal <0>
● at AC at 230 V maximum permissible
7mA
● at DC at 24 V maximum permissible
16mA
Auxiliary circuit:
3RT2026-2KF40 Changes preserved
Page 4/