Datasheet

— at 400 V rated value
23kW
— at 400 V at 60 °C rated value
23kW
— at 690 V rated value
40kW
— at 690 V at 60 °C rated value
40kW
● at AC-2 at 400 V rated value
11kW
● at AC-3
— at 230 V rated value
5.5kW
— at 400 V rated value
11kW
— at 690 V rated value
11kW
Operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value
4.4kW
● at 690 V rated value
7.7kW
Thermal short-time current limited to 10 s 200A
Power loss [W] at AC-3 at 400 V for rated value of
the operating current per conductor
1.6W
No-load switching frequency
● at DC
15001/h
Operating frequency
● at AC-1 maximum
10001/h
● at AC-2 maximum
7501/h
● at AC-3 maximum
7501/h
● at AC-4 maximum
2501/h
Control circuit/ Control:
Type of voltage of the control supply voltage DC
Control supply voltage at DC
● rated value
110V
Operating range factor control supply voltage rated
value of magnet coil at DC
0.7...1.25
Design of the surge suppressor with varistor
Closing power of magnet coil at DC 4.5W
Holding power of magnet coil at DC 4.5W
Closing delay
● at DC
50...170ms
Opening delay
● at DC
15...17.5ms
Arcing time 10...10ms
Residual current of the electronics for control with
signal <0>
● at AC at 230 V maximum permissible
7mA
● at DC at 24 V maximum permissible
16mA
Auxiliary circuit:
3RT2026-2KF40 Changes preserved
Page 4/
10
06.04.2016 © Copyright Siemens AG