Datasheet
— at 690 V rated value
40kW
— at 690 V at 60 °C rated value
40kW
● at AC-2 at 400 V rated value
5.5kW
● at AC-3
— at 230 V rated value
3kW
— at 400 V rated value
5.5kW
— at 690 V rated value
7.5kW
Operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value
2.6kW
● at 690 V rated value
4.6kW
Thermal short-time current limited to 10 s 110A
Power loss [W] at AC-3 at 400 V for rated value of
the operating current per conductor
0.5W
No-load switching frequency
● at DC
15001/h
Operating frequency
● at AC-1 maximum
10001/h
● at AC-2 maximum
10001/h
● at AC-3 maximum
10001/h
● at AC-4 maximum
3001/h
Control circuit/ Control:
Type of voltage of the control supply voltage DC
Control supply voltage at DC
● rated value
24V
Operating range factor control supply voltage rated
value of magnet coil at DC
0.8...1.1
Closing power of magnet coil at DC 5.9W
Holding power of magnet coil at DC 5.9W
Closing delay
● at DC
50...170ms
Opening delay
● at DC
15...17.5ms
Arcing time 10...10ms
Residual current of the electronics for control with
signal <0>
● at AC at 230 V maximum permissible
6mA
● at DC at 24 V maximum permissible
16mA
Auxiliary circuit:
Number of NC contacts
● for auxiliary contacts
— instantaneous contact
1
3RT2024-1BB40 Changes preserved
Page 4/
10