Datasheet

— at 690 V rated value
40kW
— at 690 V at 60 °C rated value
40kW
● at AC-2 at 400 V rated value
4kW
● at AC-3
— at 230 V rated value
2.2kW
— at 400 V rated value
4kW
— at 690 V rated value
7.5kW
Operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value
2kW
● at 690 V rated value
2.5kW
Thermal short-time current limited to 10 s 80A
Power loss [W] at AC-3 at 400 V for rated value of
the operating current per conductor
0.4W
No-load switching frequency
● at AC
50001/h
Operating frequency
● at AC-1 maximum
10001/h
● at AC-2 maximum
10001/h
● at AC-3 maximum
10001/h
● at AC-4 maximum
3001/h
Control circuit/ Control:
Type of voltage of the control supply voltage AC
Control supply voltage at AC
● at 50 Hz rated value
110V
Operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz
0.8...1.1
Apparent pick-up power of magnet coil at AC
● at 50 Hz
65V·A
Inductive power factor with closing power of the coil
● at 50 Hz
0.82
Apparent holding power of magnet coil at AC
● at 50 Hz
7.6V·A
Inductive power factor with the holding power of the
coil
● at 50 Hz
0.25
Closing delay
● at AC
9...38ms
Opening delay
● at AC
4...16ms
Arcing time 10...10ms
3RT2023-1AF00 Changes preserved
Page 4/
10
08.04.2016 © Copyright Siemens AG