Datasheet

standard mounting rail according to DIN EN
50022
Type of fixing/fixation / series installation
Yes
Width
mm 45
Height
mm 57.5
Depth
mm 72
Distance, to be maintained, to the ranks assembly
forwards
mm 0
backwards
mm 0
upwards
mm 6
downwards
mm 6
sidewards
mm 0
Distance, to be maintained, to earthed part
forwards
mm 6
backwards
mm 0
upwards
mm 6
downwards
mm 6
sidewards
mm 6
Distance, to be maintained, conductive elements
forwards
mm 6
backwards
mm 6
upwards
mm 6
downwards
mm 10
sidewards
mm 6
Connections:
Design of the electrical connection
for main current circuit
screw-type terminals
for auxiliary and control current circuit
screw-type terminals
Type of the connectable conductor cross-section
for main contacts
solid
2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2), 2x 4
mm2
stranded
2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2), 2x 4
mm2
finely stranded
with conductor end processing
2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2)
for AWG conductors / for main contacts
2x (20 ... 16), 2x (18 ... 14), 2x 12
for auxiliary contacts
solid
2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2), 2x 4
mm2
finely stranded
with conductor end processing
2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2)
for AWG conductors / for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14), 2x 12
Certificates/approvals:
Verification of suitability
CE / UL / CSA / CCC
Safety:
B10 value / with high demand rate
according to SN 31920
1000000
T1 value / for proof test interval or service life
according to IEC 61508
a 20
Proportion of dangerous failures
with low demand rate / according to SN
31920
% 40
with high demand rate / according to SN
% 75
http://support.automation.siemens.com/WW/view/en/33238686&td=1
Page 4 of 6 3/30/2012 9:07:02 AM