Datasheet
Closing delay
at DC
ms 30…100
Opening delay
at DC
ms 7…13
Arcing time
ms 10…15
Auxiliary circuit:
Contact reliability / of the auxiliary contacts
1 faulty switching per 100 million (17 V, 1 mA)
Number of NC contacts / for auxiliary contacts /
instantaneous switching
0
Number of NO contacts / for auxiliary contacts /
instantaneous switching
1
Operating current / of the auxiliary contacts
at AC-12 / maximum
A 10
at AC-15
at 230 V
A 6
at 400 V
A 3
at DC-12
at 48 V
A 6
at 60 V
A 6
at 110 V
A 3
at 220 V
A 1
at DC-13
at 24 V
A 6
at 48 V
A 2
at 60 V
A 2
at 110 V
A 1
at 220 V
A 0.3
Short-circuit:
Design of the fuse link
for short-circuit protection of the auxiliary
switch / required
fuse gL/gG: 10 A
for short-circuit protection of the main
circuit
with type of assignment 1 / required
gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED
5SE: 35 A
at type of coordination 2 / required
gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED
5SE: 20A
Installation/mounting/dimensions:
Built in orientation
vertical
Type of mounting
screw and snap-on mounting onto 35 mm
standard mounting rail according to DIN EN
50022
Type of fixing/fixation / series installation
Yes
Width
mm 45
Height
mm 57.5
Depth
mm 73
Distance, to be maintained, to the ranks assembly /
sidewards
mm 0
Distance, to be maintained, to earthed part / sidewards
mm 6
Connections:
Design of the electrical connection
for main current circuit
screw-type terminals
for auxiliary and control current circuit
screw-type terminals
Type of the connectable conductor cross-section
for main contacts
http://support.automation.siemens.com/WW/view/en/33239267&td=1
Page 3 of 6 3/30/2012 8:57:30 AM