Datasheet
Operating current
at AC-1 / at 400 V
at 40 °C ambient temperature / rated
value
A 22
at 60 °C ambient temperature / rated
value
A 20
at AC-2 / at 400 V / rated value
A 12
at AC-3 / at 400 V / rated value
A 12
at AC-4 / at 400 V / rated value
A 8.5
Operating current
with 1 current path / at DC-1
at 24 V / rated value
A 20
at 110 V / rated value
A 2.1
with 2 current paths in series / at DC-1
at 24 V / rated value
A 20
at 110 V / rated value
A 12
with 3 current paths in series / at DC-1
at 24 V / rated value
A 20
at 110 V / rated value
A 20
with 1 current path / at DC-3 / at DC-5
at 24 V / rated value
A 20
at 110 V / rated value
A 0.1
with 2 current paths in series / at DC-3 / at
DC-5
at 24 V / rated value
A 20
at 110 V / rated value
A 0.35
with 3 current paths in series / at DC-3 / at
DC-5
at 24 V / rated value
A 20
at 110 V / rated value
A 20
Service power
at AC-2 / at 400 V / rated value
kW 5.5
at AC-3 / at 400 V / rated value
kW 5.5
at AC-4 / at 400 V / rated value
kW 4
Active power loss / per conductor / typical
W 1.2
Off-load operating frequency
at AC
1/h 10,000
at DC
1/h 10,000
Frequency of operation / at AC-1 / according to IEC
60947-6-2
1/h 1,000
Frequency of operation / at AC-2 / according to IEC
60947-6-2
1/h 750
Frequency of operation / at AC-3 / according to IEC
60947-6-2
1/h 750
Frequency of operation / at AC-4 / according to IEC
60947-6-2
1/h 250
Control circuit:
Design of the surge suppressor
with diode
Type of voltage / of the controlled supply voltage
DC
Control supply voltage / 1
for DC / rated value
V 24
operating range factor control supply voltage rated
value / of the magnet coil
for DC
0.8…1.1
Pull-in power / of the solenoid / for DC
W 4
Holding power / of the solenoid / for DC
W 4