Datasheet

● at 50 Hz rated value
110V
● at 60 Hz rated value
110V
Operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz
0.8...1.1
● at 60 Hz
0.85...1.1
Apparent pick-up power of magnet coil at AC
● at 50 Hz
37V·A
● at 60 Hz
33V·A
Inductive power factor with closing power of the coil
● at 50 Hz
0.8
● at 60 Hz
0.75
Apparent holding power of magnet coil at AC
● at 50 Hz
5.7V·A
● at 60 Hz
4.4V·A
Inductive power factor with the holding power of the
coil
● at 50 Hz
0.25
● at 60 Hz
0.25
Closing delay
● at AC
8...33ms
Opening delay
● at AC
4...15ms
Arcing time 10...15ms
Control version of the switch operating mechanism Standard A1 - A2
Auxiliary circuit
Number of NO contacts for auxiliary contacts
● instantaneous contact
1
Operating current at AC-12 maximum 10A
Operating current at AC-15
● at 230 V rated value
10A
● at 400 V rated value
3A
● at 500 V rated value
2A
● at 690 V rated value
1A
Operating current at DC-12
● at 24 V rated value
10A
● at 48 V rated value
6A
● at 60 V rated value
6A
● at 110 V rated value
3A
● at 125 V rated value
2A
● at 220 V rated value
1A
● at 600 V rated value
0.15A
3RT2017-1AF01 Subject to change without notice
Page 5/
12
08/20/2019 © Copyright Siemens