Datasheet

• at 110 V A 1
• at 220 V A 0.3
Short-circuit:
Design of the fuse link
• for short-circuit protection of the auxiliary switch / required fuse gL/gG: 10 A
• for short-circuit protection of the main circuit
• with type of assignment 1 / required gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35
A
• at type of coordination 2 / required gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE:
20A
Installation/mounting/dimensions:
Built in orientation vertical
Type of mounting screw and snap-on mounting onto 35 mm standard
mounting rail according to DIN EN 50022
Type of fixing/fixation / series installation Yes
Width mm 45
Height mm 57.5
Depth mm 73
Distance, to be maintained, to the ranks assembly / sidewards mm 0
Distance, to be maintained, to earthed part / sidewards mm 6
Connections:
Design of the electrical connection
• for main current circuit screw-type terminals
• for auxiliary and control current circuit screw-type terminals
Type of the connectable conductor cross-section
• for main contacts
• solid 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
• finely stranded
• with conductor end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
• for AWG conductors / for main contacts 2x (20 ... 16), 2x (18 ... 14), 2x 12
• for auxiliary contacts
• solid 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
• finely stranded
• with conductor end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
• for AWG conductors / for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14), 2x 12
Certificates/approvals:
3RT2016-1FB41
Page 4/ 03/30/2012
subject to modifications
© Copyright Siemens AG 2012
7