Datasheet

— with type of coordination 1 required
gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 35 A
— with type of assignment 2 required
gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 20 A
● for short-circuit protection of the auxiliary switch
required
fuse gG: 10 A
Installation/ mounting/ dimensions
Mounting position +/-180° rotation possible on vertical mounting surface; can be
tilted forward and backward by +/- 22.5° on vertical mounting
surface
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
● Side-by-side mounting
Yes
Height 70mm
Width 45mm
Depth 73mm
Required spacing
● for grounded parts
— at the side
6mm
● for live parts
— at the side
6mm
Connections/Terminals
Type of electrical connection
● for main current circuit
spring-loaded terminals
● for auxiliary and control current circuit
spring-loaded terminals
Type of connectable conductor cross-sections
● for main contacts
— solid
2x (0.5 ... 4 mm²)
— single or multi-stranded
2x (0,5 ... 4 mm²)
— finely stranded with core end processing
2x (0.5 ... 2.5 mm²)
— finely stranded without core end
processing
2x (0.5 ... 2.5 mm²)
● at AWG conductors for main contacts
2x (20 ... 12)
Connectable conductor cross-section for main
contacts
● solid
0.5...4mm²
● stranded
0.5...4mm²
● finely stranded with core end processing
0.5...2.5mm²
● finely stranded without core end processing
0.5...2.5mm²
Connectable conductor cross-section for auxiliary
contacts
● single or multi-stranded
0.5...4mm²
● finely stranded with core end processing
0.5...2.5mm²
● finely stranded without core end processing
0.5...2.5mm²
3RT2015-2BB41 Subject to change without notice