Datasheet
Operating current
at AC-1 / at 400 V
at 40 °C ambient temperature / rated
value
A 18
at 60 °C ambient temperature / rated
value
A 16
at AC-2 / at 400 V / rated value
A 7
at AC-3 / at 400 V / rated value
A 7
at AC-4 / at 400 V / rated value
A 6.5
Operating current
with 1 current path / at DC-1
at 24 V / rated value
A 15
at 110 V / rated value
A 1.5
with 2 current paths in series / at DC-1
at 24 V / rated value
A 15
at 110 V / rated value
A 8.4
with 3 current paths in series / at DC-1
at 24 V / rated value
A 15
at 110 V / rated value
A 15
with 1 current path / at DC-3 / at DC-5
at 24 V / rated value
A 15
at 110 V / rated value
A 0.1
with 2 current paths in series / at DC-3 / at
DC-5
at 24 V / rated value
A 15
at 110 V / rated value
A 0.25
with 3 current paths in series / at DC-3 / at
DC-5
at 24 V / rated value
A 15
at 110 V / rated value
A 15
Service power
at AC-2 / at 400 V / rated value
kW 3
at AC-3 / at 400 V / rated value
kW 3
at AC-4 / at 400 V / rated value
kW 3
Active power loss / per conductor / typical
W 0.4
Off-load operating frequency
at AC
1/h 10,000
at DC
1/h 10,000
Frequency of operation / at AC-1 / according to IEC
60947-6-2
1/h 1,000
Frequency of operation / at AC-2 / according to IEC
60947-6-2
1/h 750
Frequency of operation / at AC-3 / according to IEC
60947-6-2
1/h 750
Frequency of operation / at AC-4 / according to IEC
60947-6-2
1/h 250
Control circuit:
Design of the surge suppressor
with diode
Type of voltage / of the controlled supply voltage
DC
Control supply voltage / 1
for DC / rated value
V 24
operating range factor control supply voltage rated
value / of the magnet coil
for DC
0.8…1.1
Pull-in power / of the solenoid / for DC
W 4
Holding power / of the solenoid / for DC
W 4
http://support.automation.siemens.com/WW/view/en/33236621&td=1
Page 2 of 6 3/30/2012 9:21:33 AM