Datasheet
— at 690 V rated value
4kW
Operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value
1.15kW
● at 690 V rated value
1.15kW
Thermal short-time current limited to 10 s 56A
Power loss [W] at AC-3 at 400 V for rated value of
the operating current per conductor
0.4W
No-load switching frequency
● at AC
100001/h
Operating frequency
● at AC-1 maximum
10001/h
● at AC-2 maximum
7501/h
● at AC-3 maximum
7501/h
● at AC-4 maximum
2501/h
Control circuit/ Control:
Type of voltage of the control supply voltage AC
Control supply voltage at AC
● at 50 Hz rated value
24V
● at 60 Hz rated value
24V
Operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz
0.8...1.1
● at 60 Hz
0.85...1.1
Apparent pick-up power of magnet coil at AC
● at 50 Hz
27V·A
● at 60 Hz
31.7V·A
Inductive power factor with closing power of the coil
● at 50 Hz
0.8
● at 60 Hz
0.81
Apparent holding power of magnet coil at AC
● at 50 Hz
4.2V·A
● at 60 Hz
4.8V·A
Inductive power factor with the holding power of the
coil
● at 50 Hz
0.25
● at 60 Hz
0.25
Closing delay
● at AC
9...35ms
Opening delay
● at AC
3.5...14ms
Arcing time 10...15ms
3RT2015-1AB01 Changes preserved
Page 4/
10
05.04.2016 © Copyright Siemens AG