Datasheet

Control supply voltage at DC
● rated value
24V
Operating range factor control supply voltage rated
value of magnet coil at DC
0.85...1.1
Closing power of magnet coil at DC 3.3W
Holding power of magnet coil at DC 3.3W
Auxiliary circuit:
Number of NC contacts
● for auxiliary contacts
— instantaneous contact
0
Number of NO contacts
● for auxiliary contacts
— instantaneous contact
0
Operating current at AC-12 maximum 10A
Operating current at AC-15
● at 230 V rated value
6A
● at 400 V rated value
3A
Operating current at DC-12
● at 60 V rated value
6A
● at 110 V rated value
3A
● at 220 V rated value
1A
Operating current at DC-13
● at 24 V rated value
10A
● at 60 V rated value
2A
● at 110 V rated value
1A
● at 220 V rated value
0.3A
Contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
Short-circuit protection
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of assignment 1 required
fuse gL/gG: 35 A
— with type of assignment 2 required
fuse gL/gG: 20 A
● for short-circuit protection of the auxiliary switch
required
fuse gL/gG: 10 A
Installation/ mounting/ dimensions:
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 50022
● Side-by-side mounting
Yes
Height 57.5mm
Width 45mm
Depth 72mm
3RT1317-1BB40 Changes preserved
Page 3/
6
17.02.2016 © Copyright Siemens AG