Datasheet

Control circuit/ Control:
Type of voltage of the control supply voltage AC
Control supply voltage at AC
● at 50 Hz rated value
230V
● at 60 Hz rated value
230V
● rated value
50Hz
Control supply voltage frequency 2 rated value 60Hz
Operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz
0.8...1.1
● at 60 Hz
0.85...1.1
Apparent pick-up power of magnet coil at AC 27V·A
Inductive power factor with closing power of the coil 0.8
Apparent holding power of magnet coil at AC 4.4V·A
Inductive power factor with the holding power of the
coil
0.27
Auxiliary circuit:
Number of NC contacts
● for auxiliary contacts
— instantaneous contact
0
Number of NO contacts
● for auxiliary contacts
— instantaneous contact
1
Operating current at AC-12 maximum 10A
Operating current at AC-15
● at 230 V rated value
6A
● at 400 V rated value
3A
Operating current at DC-12
● at 60 V rated value
6A
● at 110 V rated value
3A
● at 220 V rated value
1A
Operating current at DC-13
● at 24 V rated value
10A
● at 60 V rated value
2A
● at 110 V rated value
1A
● at 220 V rated value
0.3A
Contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
Short-circuit protection
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of assignment 1 required
fuse gL/gG: 35 A
— with type of assignment 2 required
fuse gL/gG: 20 A
3RT1015-2AP01 Changes preserved
Page 3/
6
23.02.2016 © Copyright Siemens AG