Datasheet

Control circuit/ Control:
Type of voltage of the control supply voltage AC
Control supply voltage at AC
● at 50 Hz rated value
230V
● at 60 Hz rated value
230V
● rated value
50Hz
Control supply voltage frequency 2 rated value 60Hz
Operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz
0.8...1.1
● at 60 Hz
0.85...1.1
Apparent pick-up power of magnet coil at AC 27V·A
Inductive power factor with closing power of the coil 0.8
Apparent holding power of magnet coil at AC 4.4V·A
Inductive power factor with the holding power of the
coil
0.27
Auxiliary circuit:
Number of NC contacts
● for auxiliary contacts
— instantaneous contact
0
Number of NO contacts
● for auxiliary contacts
— instantaneous contact
1
Operating current at AC-12 maximum 10A
Operating current at AC-15
● at 230 V rated value
6A
● at 400 V rated value
3A
Operating current at DC-12
● at 60 V rated value
6A
● at 110 V rated value
3A
● at 220 V rated value
1A
Operating current at DC-13
● at 24 V rated value
10A
● at 60 V rated value
2A
● at 110 V rated value
1A
● at 220 V rated value
0.3A
Contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
Short-circuit protection
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of assignment 1 required
fuse gL/gG: 35 A
— with type of assignment 2 required
fuse gL/gG: 20 A
3RT1015-2AP01 Changes preserved
Page 3/
6
23.02.2016 © Copyright Siemens AG